Disable output (B3)

Not available for users with access level / type "Information only".
Up to 100 control outputs, except outputs of type "alarm device",
can be individually disabled via menu B3. Disabled output will stay
in (or return to) the normal condition for the output respectively.
Log in with a User name and Password for typ Building officer (or
Service personnel), see page 5.
H1 Perform monthly test
Scroll (or press "2") to menu H2.
H2 Disable or re-enable
Press "A" to sub menu B1.
B1 Disable zone
Scroll (or press "3") to menu B3.
B3 Disable output
Press "A".
Use the keypad to select "type" of output:
0=Loop unit (3361, 3364, 3377/4477, 3379, 4380 or 4383) output.
1=C.i.e. output S0 or S1. (Default programmed as type "Alarm
device", i.e. cannot be individually disabled.)
2=C.i.e. output R0. (Default programmed as type "Routing
equipment" – Fire brigade tx, i.e. can in that case also be disabled via
menu B10.)
3=C.i.e. expansion board (4581 or 4583) output.
Press "A".
Depending on the selected type, use the keypad to type additional
data:
0: Output number (0-2)
1: Output (S)number 0-1.
2: Output (R)number 0
3: Output number (0-7) and expansion board number (0-3).
Press "A".
Disabled (or not disabled) output information is shown. Press "A".
When required, disable more outputs or press "Return" to menu B3.
Scroll to another menu or press "Return" to menu H2. Scroll to
another menu or leave the menu system by pressing "Return".
5
Regarding the units 3377/4477 and 3379: Output number 0=high priority,
1=medium priority and 2=low priority.
EBL128 version 2.0.x, Daily user's manual