Gas Piping; Venting - Kenmore POWER MISER 153.330401 Owner's Manual

Kenmore water heater user manual
Table of Contents

Advertisement

Installation
Instructions (cont'd)
Venting (cont'd)
All vent gases must be completdy vented to the outdoors of the
structure (dwelling). InstaU only the draft hood provided with
the new water heater and no other draft hood.
Vent pipes must be secured at each joint with sheet metal screws.
TO
CHIMNEY
VENT PIPE INSTALLATION
Gas Piping
AWARNING
Make sore the gas suppliedis the same type listed on the
model rating plate. The inlet gas pressuremust not exceed
14 incheswater column ½ pound per squareinch(3.SkPa).
The minimum inlet gaspressurelisted on the model ratin
plate isfor the purposeofinput adj_
AW.A.RNING
[
If the gascontrolvalveis subjected to pressures exceeding ½[
pound per square inch(3.SkPa),the damageto the gascon-[
[ trel valvecouldresultin a Ere or explosion from leakingga_
There must be a minimfim of 6" clearance between single wall
vent pipe and any combustible material. Fill and seal any clear-
ance between single wall vent pipe and combustible material
with mortar mix, cement, or other noncombustible
substance.
For other than single wall, follow vent pipe manufacturer's dear-
ance specifications. To insure a tight fit of the vent pipe in a
brick chimney, seal around the vent pipe with mortar mix
cement.
AWARNING
[
If the main gasline shutoffservingall gasappliances is used,[
alsoturn "OFF" the gasat eachappliance. L eaveall gasappli-
ancesshutoff untilthe water heater installation iscomplete.
AWARNING
Failureto haverequired clearancesbetweenvent pipingand
combustible material will resultin afire hazard.
AWARNING
[
Be sure vent pipe is properlyconnectedto preventescapeof
dangerous flue gases whichcoud causedeadlyasphyx ation.
AWARNING
Chemical vapor corrosionof the flue and vent system may
occurif air for combustion containscertain chemicalvapors.
Spray can propellants,cleaningsolvents, r efrigerator and air
conditioner refrigerants, swimmingpool chemicals,calcium
and sodiumchloride,waxes,bleach,and process chemicals are
typicalcompounds w hicharepotentially corrosive.
A gas line of sufficient size must be run to the water heater.
Consult the latest edition of National Fuel Gas Code ANSI
Z223.1, also referred to as NFPA54 and the gascompany concern-
ing pipe size.
There must be:
• A readily accessible manual shut offvalve in the gas supply line
serving the water heater, and
• A drip leg (sediment trap) ahead of the gas control valve to help
prevent dirt and foreign materials from entering the gas control
valve.
• A flexible gas connector or a ground joint union between the
shutoffvalve and control valve to permit servicing of the unit.
Be sure to check all the gas piping for leaks before lighting the
water heater. Use a soapy water solution,
not a match or open
flame. Rinse offsoapy solution and wipe dry.
Standard
Models are for installation
up to 3,300 feet above sea
level.
High Altitude
Models are for installation
from 3,300 to 5,500
feet above sea level.
Ifa standard model is installed above 3,300 feet or a high altitude
model is installed
above 5,500 feet, the input
rating must be
reduced at the rate of 4 percent for each 1,000 feet above sea level.
Contact your local Sears Service Center or gas utility for forther
information.
AWARNING
The appliance and its gas connection must be leak tested
beforeplacngthe appliancein operation.
14