Gas Piping - Kenmore POWER MISER 8 Owner's Manual

Hide thumbs Also See for POWER MISER 8:
Table of Contents

Advertisement

Installation
Instructions
(cont'd)
Venting
(cont'd)
All vent gases must be completely vented to the outdoors of the
structure (dwelling,). Iustal[only the dra_ hood provided with
the new water heater and no other drafthood.
Vent pipes must be secured at each joint with sheet metal screws.
TO
CHIMNEY
I
t
VENT PIPE INSTALLATION
There must be a minimum
of 6" clearance between single wall
vent pipe and any combustible
material. Fill and seal any clear-
ance between
single wall vent pipe and combustible
material
with mortar mix, cement,
or other noncombustible
substance.
For other than single wall, follow vent pipe manufacturer's clear-
ance specifications.
To insure a tight fit of the vent pipe in a
brick chimney,
seal around the vent pipe with mortar
mix
cement.
Gas Piping
AWARNING
Make sure the gas supplied is the same type listed on the
model rating plate. The inlet gas pressure must not exceed
14 inches w_.
column ½ pound per square inch (3_kPa)]. I
The minimum mint gas pressure listed on the mdel
rating
plate is for the purpose of input edjus_,neat.
[
I
AWARNING
I
if thegas €on valve pressures
exceeding 'A. I
pound per square inch (3.SkPa), the.damage to the gas con I
trol valve €ould result in a fire or explosionfrom leaking ga_
]
AWARNING
]
If the main gas line s_gas
appliances is used, ]
also turn "off"
the gas at each appliance. Leave all gas appli- |
ances sbut off until the water heator installation is complete. ]
AWARNING
Failureto haverequiredclearances betweenvent pipingand I
combustible materialwill resultin a fire hazard.
AWARNING
[
Be sureventpipeisproperlyconnected to preventescapeof
dangerous fluegases which couldcausedeadlyasphyxiation.
AWARNING
Chemicalvapor corrosionof the flue and vent systemmay
occurif air for combustion contains certain chemical v apors.
Spraycan propellants, cleaningsolvents, r efrigerator and air
conditionerrefrigerants, swimmingpool chemicals, c alcium
and sodium chloride,waxes, b leach, a nd process c hemicals a re
typical c ompounds w hich are potentiallycorrosive.
A gas line of sufficient size must be run to the water heater.
Consult the latest edition of National Fuel Gas Code ANSI
Z223.1, also referred to as NFPA54 and the gas company concern-
ing pipe size.
There must be:
• A readily accessible manual shut off valve in the gas supply line
serving the water heater, and
• A drip leg (sediment trap) ahead of the gas control valve to help
prevent dirt and foreign materials from entering the gas control
valve.
• A flexible gas connector
or a ground joint union between the
shutoffvalve and control valve to permit servicing of the unit.
Be sure to check all the gas piping for leaks before lighting the
water heater. Use a soapy water solution, not a match or open
flame. Rinse offsoapy solution and wipe dry.
Standard
Models are for installation up to 3,300 feet above sea
level.
High Altitude
Models are for installation
from 3,300 to 5,500
feet above sea level.
Ifa standard model is installed above 3,300 feet or a high altitude
model is installed
above 5,500 feet, the input
rating must be
reduced at the rate of 4 percent for each 1,000 feet above sea level.
Contact your local Sears Service Center or gas utility for further
information.
AWARNING
I
The appliance and its gas connection
must be leak tested
before plac ng the appl ance in operation.
14