Combustion Air and Ventilation
for Appliances Located in
Unconfined Spaces
Uncon_qned Space is a space whose volume is not less than 50
cubic feet per 1,000 Btu per hour of the aggregate input rating
of all appliances installed in that space. Rooms comuiunicatin_
directly with the space in which the appliances are installed,
through openings not furnished with doors, are considered a
part of the unconfined space
In unconfined spaces in buildings, infiltration may be adequate
to provide air for combustion, ventilation and dilution of flue
gases. However, in buildings of tight construction (for example,
weather stripping, heavily insulated, caulked, vapor barrier, etc.),
additional air may need to be provided using the methods
described in Comb.ustion Air and Ventilation_ for Appliances
Located in Confined Spaces, b.
Combustion
Air and Ventilation
for Appliances Located in
Confined Spaces
Confined
Space is a space whose volume is less than 50 cubic
feet per 1,000 Btu per hour of the aggregateinput rating of all
appliances installed in that space.
a. ALL AIR FROM INSIDE BUILDINGS:
(See Page 9 Figure 1, and Figure 2 below)
The confined space shall be provided with two permanent
openings communicating directly with an additional room(s)
of sufficient volume so that the combined volume of all
spaces meets the criteria for an unconfined space. The total
input of all gas utilization equipment installed in the com-
bined space shall be considered in making this determination.
Each opening shall have a minimum free area of one square
inch per 1,000 BTU per hour of the total input rating of all
gas utilization equipment in the confined space, but not less
than 100 square inches. One opening shall commence within
12" of the top and one commencing within 12" of the bot-
tom of the enclosure.
b. ALL AIR FROM OUTDOORS:
(see Figures 3-5)
The confined space shall be provided with two permanent
openings, one commencing within 12" of the top and one
commencing within 12" from the bottom of the enclosure.
The openings shall communicate directly, or by ducts, with
the outdoors or spaces (crawl or attic) that freely communi-
cate with the outdoors.
I Figure
3 1
1. When directly communicating with the outdoolS, each open-
ing shall have a minimum free area of 1 square inch per 4,000
BTU per hour of total input rating of all equipment in the
enclosure. (See Figure 3.)
2. When communicating
with the outdoors through vertical
ducts, each opening shall have a minimum free area of 1
square inch per 4,000 BTU per hour of total input rating of
all equipment in the enclosure. (See Figure4.)
• CHIMNEY O_ _
VENT
I Figure 4 ]
10
3. When communicating with the outdoors through horizontal
ducts, each opening shall have a minimum free area of 1
square inch per 2,000 BTU per hour of total input rating of
all equipment in the enclosure. (See Figure 5.)
4. When ducts are used, they shall be of the same cross-sectional
area as the free area of the openings to which they connect.
The minimum
short side dimension
of rectangular
air ducts
shall not be less than 3". (See Figure 5.)
.
Louvers and Grilles: In calculating
free area, consideration
shall be given to the blocking
effect of louvers,
grilles or
screens protecting
openings. Screens used shall not be smaller
than ¼" mesh. If the free area through
a design of louver or
grille is known, it should be used in calculating
the size open-
ing required
to provide
the free area specified. If the design
and free area is not known, it may be assumed that wood lou-
vers will be 20-25 percent
free area and metal louvers
and
grilles will have 60-75 percent
free area. Louvers and grilles
shall be fixed in the open position
or interlocked
with the
equipment
so that they are opened
automatically
during
equipment
operation.
6. Special
Conditions
Created
by Mechanical
Exhausting
or
Fireplaces:
Operation
of exhaust
fans, ventilation
systems,
clothes dryers or fireplaces may create conditions
requiring
special attention
to avoid unsatisfactory
operation of installed
gas utilization
equipment.