Combustion Air And Ventilation For Appliances In Unconfined Spaces; Combustion Air And Ventilation For Appliances In Confined Spaces - Kenmore 153.330401 Owner's Manual

40, 50 & 75 gal. highaltitude, for potable water heating only not suitablefor space heating, not for use in mobile homes
Hide thumbs Also See for Kenmore 153.330401:
Table of Contents

Advertisement

Installation
Instructions
(cont'd)
Combustion
Air and Ventilation
for Appliances
Located
in
Unconfined
Spaces
Unconfined Space is a space whose volume is not less than 50
cubic feet per 1,000 Btu per hour of the aggregate input rating
of all appliances installed in that space. Rooms communicating
directly with the space in which the appliances are installed,
through openings not furnished with doors, are considered a
part of the unconfined space
In unconfined spaces in buildings, infiltration may be adequate
to provide air for combustion,
ventilation
and dilution of flue
gases. However, in buildings of tight construction (for example,
weather stripping, heavily insulated, caulked, vapor barrier, etc.),
additional air may need to be provided using the methods
described in Combustion Air and Ventilation for Appliances
Located in Confined Spaces, b.
Combustion Air and Ventilation
for Appliances Located in
Confined Spaces
Comqned Space is a space whose volume is less than 50 cubic
fdet per 1,000 Btu per hour of the aggregate input rating of all
appliances installed in that space.
a. ALL AIR FROM INSIDE BUILDINGS:
(See Page 9 Figure 1, and Figure 2 below)
The confined space shall be provided with two permanent
openings communicating directly with an additional room(s)
of sufficient volume so that the combined volume of all
spaces meets the criteria for an unconfined space. The total
input of all gas utilization equipment installed in the com-
bined space shall be considered in making this determination.
Each opening shall have a minimum free area of one square
inch per 1,000 BTU per hour of the total input rating of all
gas utilization equipment in the confined space, but not less
than 100 square inches. One opening shall commence within
12" of the top and one commencing within 12" of the bot-
tom of the enclosure.
Figure 2 ]
b. ALL AIR FROM
OUTDOORS:
(seeFigures _3-5)
The confined
space shall be providedwitfi
two permanent
openings,
one commencing
within 12 of the top and one
commencing
within 12" from the bottom of the enclosure.
The openings shall communicate
directly, or by ducts, with
the outdoors or spaces (crawl or attic) that freely communi-
cate with the outdoors.
1. When direcdy communicating
with the outdoors, each open-
ing shall have a minimum
free a_'ea of I square inch per 4,000
BTU per hour of total input rating of all equipment
in the
enclosure. (See Figure 3.)
2. When
communicating
with the outdoors
through
vertical
ducts, each opening
shall have a minimum
free area of 1
square inch per 4,000 BTU per hour of total input rating of
all equipment
in the enclosure. (See Figure 4.)
Figure 4 ]
10
3. When communicating with the outdoors through horizontal
ducts, each opening shall have a minimum free area of 1
square inch per 2,000 BTU per hour of total input rating of
all equipment in the enclosure. (See Figure 5.)
TM
I
I
....
i
roll
II
4. When ducts are used, they shall be of the same cross-sectional
area as the free area of the openings to which they connect.
The minimum short side dimension of rectangularair ducts
shall not be less than 3". (See Figure5.)
5. Louvers and Grilles: In calculating
free area, consideration
shall be given to the blocking
effect of louvers,
grilles or
screens protecting
openings. Screens used shall not be smaller
than ¼"mesh.
If the free area through a design of louver or
grille is known, it should be used in calculating the size open-
ing required to provide the free area specified. If the design
and free area is not known, it may be assumed that wood lou-
vers will be 20-25 percent
free area and metal louvers and
grilles will have 60-75 percent
free area. Louvers and grilles
shall be fixed in the open position
or interlocked
with the
equipment
so that they are opened
automatically
during
eqmpment
operation.
6. Special Conditions
Created
by Mechanical
Exhausting
or
Fireplaces: Operation
of exhaust
fans, ventilation
systems,
clothes dryers or fireplaces may create conditions
requiting
special attention to avoid unsatisfactory
operation of installed
gas utilization equipment.

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents