Locating The New Water Heater - Kenmore 153.335863 Owner's Manual

Power vent gas water heater
Table of Contents

Advertisement

Installation
Instructions
Locating the New Water
Heater
You should carefully choose an indoor location for the new water
heater, because
the placement
is a very important
consideration
for the safety of the occupants
in the building
and for the most
economical
use of the appliance.
This water heater
is not for
use in mobile
homes or outdoor
installation.
Whether
replacing
an old water heater
or putting
the water
heater in a new location,
the following
critical points
must be
observed.
1. The location
selected should
be indoors as close as practical
to the vent termination
point,
and as centralized
with the
water piping system as possible. The water heater, as all water
heaters, will eventually
leak. Do not install without
adequate
drainage
provisions
where water flow will cause damage.
2. If vented
through
an outside
wall or through
the roof the
vent piping cannot exceed a total of 35 feet including
vertical
and horizontal
runs and have no more than 3 elbows. It can-
not slope downward
and horizontal
runs require ¼" per foot
rise. All horizontal
runs require adequate
support
at 3_ feet
intervals.
3. The water heater requires
i_s own (separate) venting system.
It cannot
be connected
to an existing vent pipe or chimney.
It must terminate
to the outdoors.
Whenever
possible
termi-
nate the vent on the leaward side of the building
if vented
through
an outside wall. NOTE:
Condensation
may be cre-
ated, at times,
as the combustion
gases exit the vent cap
and discoloration
of surfaces
in proximity
to the vent cap
may occur.
AWARNING
The powerventwater heaterrequires itsown(separate)venting
system.It cannotbeconnected to an existing ventpipeor chim-
ney.It mustbeterminatedto theoutdoors, F ailureto pmperlyin-
stallthe venting system canresult in asphyxiation, a fire or explo-
sionand can causeDEATH, SERIOUS BODILY INJURY,OR
PROPERTYDAMAGE.
4. The water hearer comes equipped with a 5 foot power cord
which can be used to connect to a 110/120 volt power
source if (1) local codes allow, and (2) there is a three prong
receptacle available.
A WARNING
Do not usean extension cord. If there isnot a suitable recepta-
cle and/or localcodes prohibituseof a powercord,fieldwiring
mustbe provided.
ACAUTION
WATER HEATERS EVENTUALLY
LEAK: Installation of the
water heater must be accomplished in such a manner that if
the tank or any connections should leak, the flow of water
will not cause damage to the structure. For this reason, it is
not advisable to install the water heater in at attic or upper
floor. When such locations cannot be avoided, a suitable
drain pan should be installed under the water heater. Drain
pans are available at your local Sears store. Such a drain pan
must be not greater than I% inches deep, have a minimum
length and width of at least 2 inches greater than the water
heater dimensions and must be piped to an adequate drain.
The pan must not restrict combustion air flow. Under no cir-
cumstances is the manufacturer
or Sears to be held liable
for any water damage in connection with this water heater.
5. The location selection
must provide
adequate
clearances
for
servicing and proper operation
of the water heater.
AWARNING
INSTALLATIONSIN AREASWHERE FLAMMABLELIQUIDS
(VAPORS) ARE LIKELY TO BE PRESENT OR STORED
(GARAGES, STORAGE, AND UTILITY
AREAS, ETC):
Flammableliquids(suchas gasoline, s olvents, p ropane(LP) or
butane, etc.), all of which emit flammable vapors, may be
improperlystoredor usedin suchareas.The gaswater heater
pilot lightor ma_nbumer canignitesuchvapors. T he resulting
flashback andfire cancausedeath or serious burnsto anyonein
the area,aswellaspropertydamage.
If installation in suchareasisyouronlyoption,then the installa-
tion must be accomplished in a way that the pilot flame and
main burnerflameare elevated from the floor at least18inches.
While this may reduce the chances of flammablevaporsfrom a
floor spillbeing ignited, g asoline and otherflammable substances
shouldneverbe storedor usedin the sameroom or areacon-
taininga gaswater heateror otheropenflameor sparkproduc-
ingappliance.
NOTE: Flammablevaporsmay be drawnby air currentsfrom
otherareasofthe structure to theappliance.
AWARNING
Propellantsof aerosolspraysand volatilecompounds,(clean-
ers, chlorinebasedchemicals, r efrigerants, etc.) in additionto
beinghighlyflammable in manycases, w ill alsochangeto cor-
rosive hydrochloricacid when exposedto the combustion
productsof the water heater. The results can be hazardous,
and alsocauseproductfailure.
A WARNING
This water heater must not be installeddirectlyon carpeting.
Carpeting must be protected by a metal or wood panel
beneath the applianceextending beyond the full width and
depth of the appliance by at least 3 inches(76.2mm) in any
direction,or if the applianceis installedin an alcoveor closet,
the entire floor mustbe coveredby the panel.Failureto heed
this warningmay result in a fire hazard.
AWARNING
Minimum clearances between the water heater and com-
bustibleconstructionare 0" at the sidesand rear, 5" at the
front, and 0" from the vent pipe.Clearancefrom the top of the
jacketis 14"on mostmodels.Note that a lesser dimension may
be allowed on some models.Refer to the labelon the water
heateradjacentto the gascontrolvalvefor all clearances.
12" MAX
VENTILATION
AIR
OPENINGS
Figure I ]
_'_N
[1' MIN
MI
N'(!_ M IN.
TOP VIEW
1 I
OF CLOSET
TOP VIEW 1 ' MIN
WITHOUT OOOR
OF CLOSET
'_2" MAX.
WITH DOOR
AlE DUCT