Venting - Kenmore 153.335863 Owner's Manual

Power vent gas water heater
Table of Contents

Advertisement

Installation
Instructions
(cont'd)
Venting (cont'd)
ALL MODELS
3" PVC Schedule 40 vent piping:
1. A 3" ABS Schedule 40-45 ° vent cap with wire screen is sup-
plied with the water heater.
2. A 5' section of 3" PVC Schedule 40 pipe (more may be
required and must be supplied locally).
3. 3" PVC, ABS or CPVC Schedule 40 piping and fittings are
acceptable materials for the vent system on all 40 gallon
models and 50 gallon 40,000 BTU/HR models.
ALL 40 GALLON
AND
50 GALLON
40,000
BTU/HR
MODELS
_
OPTIONAL
2" VENT
PIPING
2" PVC Schedule 40 vent piping:
1. A wire screen to fit a 2" Schedule 40-45 ° vent cap is supplied
with the water heater.
2. A 3" PVC Schedule
40 pi!_e, minimum
length of 3" (must
be supplied locally).
3. A 3" to 2" PVC
Schedule
40 reducer
(must
be supplied
locally).
4. 2" and 3" PVC, ABS, or CPVC
Schedule
40 piping and fit-
tings are acceptable materials
for the vent system on all 40
gallon and 50 gallon 40,000
BTU/HR
models and must be
supplied
locally.
2" SCHEDULE 40 PVC PIPE
[_
3" TO 2" PVC REDUCER
]
3" SCHEDULE 40 PVC PIPE
(MINIMUM LENGTH 3")
I
I
21