When The Outdoor Unit Does Not Operate - Samsung AQ07A1VE Service Manual

Room air conditioner
Hide thumbs Also See for AQ07A1VE:
Table of Contents

Advertisement

Troubleshooting
5-2-3 When the Outdoor Unit Does Not Operate. (Initial Diagnosis)
1) Checklist :
(1) Is input voltage normal?
(2) Is the set temperature of the remote control higher than room temperature in COOL mode?
(3) Is the set temperature of the remote control lower than room temperature in HEAT mode?
(4) Is the POWER IN connector (terminal-tab) linked correctly?
(5) Is the outdoor unit properly connected with the TERMINAL BLOCK connector(5P)?
2) Troubleshooting procedure
After unplugging out the power cord should be
reconnected within five seconds.
Does the operating lamp blink
Does the timer lamp blink during operation ?
Is the power relay RY71 operated by adjusting the room
temperature?
Test rod location
+
-
IC1 Pin No.63
GND
YES
Is rating voltage ±10% range applied relay between Terminal
Tap(TB71) and RY 71 terminal No.
YES
5-4
NO
YES
YES
NO
NO
!
Normal
Condition
Voltage
RY73 ON
DC 4.8V
#
NO
!
Is the room sensor normal register?
10°C
17.96k
Check as in the procedure "No Power parts"
Refer to page 5-2.
Room temperature sensor is
out of order
@
Microcomputer is
out of order.
YES
#
Power relay is
out of order
Outdoor unit is
out of order.
NO
@
20°C
30°C
12.09k
8.3k
YES
#
PCB should be checked.
PCB should be
checked.
Power relay should be
replaced.
Samsung Electronics

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents