Built -In Sensor Configuration; Adding A Hc60Ng Zone Valve Controller; Resetting A Bound Hr80Uk - Honeywell YZ667A1060 Installation Manual

Honeywell wireless domestic heating zoning system
Hide thumbs Also See for YZ667A1060:
Table of Contents

Advertisement

8.2a Binding HR80UK Radiator Controllers to the HC60NG Boiler Module
13
To put the HC60NG in the listening
mode press the button on the HC60NG
for 5 seconds (Red LED flashes 0.5 sec
on/off).

8.3 Built -in sensor configuration

The CM67z Room Unit features a built-in temperature sensor
used for specific applications. Sensor operation is defined by
parameter 6:tS in Installer mode:
6:tS = 0 (Factory default. The built-in sensor is idle - not
used for control nor measurement).
6:tS =  (The built-in sensor is used only for measuring
the room temperature)
The symbol displayed next to the room temperature value indi-
cates that the sensor is used for measurement only and the
temperature in the room is controlled by the HR80UK Radiator
Controller. Due to different locations of the CM67z Room Unit
and HR80UK Radiator Controller
there may be a difference between
the setpoint displayed by the CM67z
Room Unit and the measured tem-
perature value.
6:tS =2 (The built-in sensor is used to
measure and control the room temper-
ature in zone 1 or when a zone valve
is used in zone ) The CM67z Room
Unit must be located in zone 1.
To complete the configuration you must set the 7:SU param-
eter to decide which system components will use the tempera-
ture value from the CM67z Room Unit:
7:SU = 0 - HR80UK's only (factory default)
7:SU =  - HC60NG (zone valve controller) only,
HR80UK's will use their own built-in sensor.
7:SU = 2 - both HR80UK's and HC60NG.

8.5 Resetting a Bound HR80UK

1
a
Turn the locking knob
and seperate
a
the operating unit and coupling module.
14
DAY 1...7
COPY
DAY
5 secs.
Bind HR80UK Radiator Controllers to
the Boiler Module :-
Move slider to OFF Position.
1
Press and hold Temp
2
Prog 1 buttons together.
z 1
z 2
AUTO
MAN
OFF
AUTO
z 1
z 2
AUTO
MAN
OFF
AUTO
2
Lift battery cover and remove one of the
batteries.
Section 8: Changing the Configuration (cont.)
MON
TUE
WED
THU
FRI
SAT
SUN
z 1
z 2
z 1
z 2
AM
PM
TEMP
AUTO
MAN
OFF
AUTO
MAN OFF

2
3
4
5
6
PROG
MAN
z 1
MAN
z 2
DATE
/
PROG
z 1
PROG
z 2
AUTO
OFF
,
and

8.4 Adding a HC60NG Zone valve controller

The HC60NG relay module can also be configured for control-
ling a zone valve. This is restricted to zone 1 only.
Before the binding procedure is started the following CM67z
Room Unit parameters need to be set in order to control the
zone 1 temperatures via the HC60NG as zone valve controller:
Enter the installer mode of the CM67z Room Unit and set the
installer parameters: 6:tS =, 9:Sn =, 7:SU = or 2 (see
Built-in sensor configuration).
a. Thermal actuator
MAN OFF
NOTE:
Install in accordance with local wiring regulations
CAUTION:
MAN OFF
Observe ambient temperature and current limits (see HC60NG wiring label)
Activating HC60NG Relay Module binding procedure
Press and hold the push button of the HC60NG Relay Module
for 5 sec to enter the binding mode. The red LED will flash at
0.5 sec on/0.5 sec off.
Activate the binding procedure at the CM67z Room Unit as
described in section 8.2 for zone . When binding information
is received correctly the red LED of the zone valve controller
will be switched off.
9
15
DAY 1...7
MON
TUE
WED
THU
FRI
SAT
SUN
z 1
z 2
z 1
z 2
AM
PM
TEMP
COPY
AUTO
MAN
OFF
AUTO
MAN OFF
DAY

2
3
4
5
6
PROG
MAN
z 1
MAN
z 2
DATE
/
PROG
z 1
PROG
z 2
AUTO
OFF
Press the Holiday Button
1
select Boiler Teach-in Mode.
Press
to send Binding Signal.
z 1
z 2
2
With a successful teach-in the red LED
will remain off (no longer flash).
b. Zone valve
c. Zone valve
3
B i n d i n g
Button
Press and hold the Binding Button while
reinserting the battery.
Now follow steps
5
to
12
on page 8.
to