Diagnosis / Faults and Alarms
F35883
CU DRIVE-CLiQ: Hardware defect
Reaction:
OFF2
Cause:
DRIVE-CLiQ communication between control unit and at least one other component is
defective.
Fault value
Bit 0 - 7: Number of the affected component
(r0949):
Bit 8 - 31: Reserved
Remedy:
- Replace Control Unit.
Acknowl.:
Immediate
F35884
CU DRIVE-CLiQ: Redundancy link error
Reaction:
OFF2
Cause:
Reserved for later use.
Remedy:
Reserved for later use.
Acknowl.:
Immediate
F35885
CU DRIVE-CLiQ: fault in cyclic data transfer
Reaction:
OFF2
Cause:
DRIVE-CLiQ communication between control unit and at least one other component is
defective.
Fault value
Bit 0 - 7: Number of the affected component
(r0949):
Bit 8 - 31: Reserved
Remedy:
- Check firmware states of affected components.
- Replace affected component.
Acknowl.:
Immediate
F35886
CU DRIVE-CLiQ: Data transfer faulted
Reaction:
OFF2
Cause:
DRIVE-CLiQ communication between control unit and at least one other component is
defective.
Fault value
Bit 0 - 7: Number of the affected component
(r0949):
Bit 8 - 31: Reserved
Remedy:
- Check firmware states of affected components.
- Replace affected component.
Acknowl.:
Immediate
F35887
CU DRIVE-CLiQ: Hardware defect
F35888
Reaction:
OFF2
Cause:
DRIVE-CLiQ communication between control unit and at least one other component is
defective.
Fault value
Bit 0 - 7: Number of the affected component
(r0949):
Bit 8 - 31: Reserved
Remedy:
Replace Control Unit.
Acknowl.:
Immediate
F35889
CU DRIVE-CLiQ: Data transfer faulted
Reaction:
OFF2
Cause:
DRIVE-CLiQ communication between control unit and at least one other component is
defective.
Fault value
Bit 0 - 7: Number of the affected component
(r0949):
Bit 8 - 31: Reserved
Remedy:
- Check for break in DRIVE-CLiQ or faulty contacts in connector.
- Check 24 V supply of affected component.
- Replace affected component.
Acknowl.:
Immediate
A35890
CU DRIVE-CLiQ: Connection setup
Cause:
DRIVE-CLiQ communication between control unit and at least one other component is
defective.