Diagnosis / Faults and Alarms
F30883
CU DRIVE-CLiQ: Hardware defect
Reaction:
OFF2
Cause:
DRIVE-CLiQ communication between control unit and at least one other component is
defective.
Fault value
Bit 0 - 7: Number of the affected component
(r0949):
Bit 8 - 31: Reserved
Remedy:
- Replace Control Unit.
Acknowl.:
Immediate
F30884
CU DRIVE-CLiQ: Redundancy link error
Reaction:
OFF2
Cause:
Reserved for later use.
Remedy:
Reserved for later use.
Acknowl.:
Immediate
F30885
CU DRIVE-CLiQ: fault in cyclic data transfer
Reaction:
OFF2
Cause:
DRIVE-CLiQ communication between control unit and at least one other component is
defective.
Fault value
Bit 0 - 7: Number of the affected component
(r0949):
Bit 8 - 31: Reserved
Remedy:
- Check firmware states of affected components.
- Replace affected component.
Acknowl.:
Immediate
F30886
CU DRIVE-CLiQ: Data transfer faulted
Reaction:
OFF2
Cause:
DRIVE-CLiQ communication between control unit and at least one other component is
defective.
Fault value
Bit 0 - 7: Number of the affected component
(r0949):
Bit 8 - 31: Reserved
Remedy:
- Check firmware states of affected components.
- Replace affected component.
Acknowl.:
Immediate
F30887
CU DRIVE-CLiQ: Hardware defect
F30888
Reaction:
OFF2
Cause:
DRIVE-CLiQ communication between control unit and at least one other component is
defective.
Fault value
Bit 0 - 7: Number of the affected component
(r0949):
Bit 8 - 31: Reserved
Remedy:
Replace Control Unit.
Acknowl.:
Immediate
F30889
CU DRIVE-CLiQ: Data transfer faulted
Reaction:
OFF2
Cause:
DRIVE-CLiQ communication between control unit and at least one other component is
defective.
Fault value
Bit 0 - 7: Number of the affected component
(r0949):
Bit 8 - 31: Reserved
Remedy:
- Check for break in DRIVE-CLiQ or faulty contacts in connector.
- Check 24 V supply of affected component.
- Replace affected component.
Acknowl.:
Immediate
F30890
CU DRIVE-CLiQ: Connection setup
Reaction:
OFF2
10-46
11/03
SINAMICS G150
Operating Manual