Pressure Units
Zero Correct
LRV Correct
URV Correct
Reset Corrects
DAC Zero Trim
Note: Loop must be
removed from
Automatic Control
DAC Span Trim
Note: Loop must be
removed from
Automatic Control
Loop Test
Note: Loop must be
removed from
Automatic Control
Page 72
atm, bar
ftH2O @ 68ºF
gf/cm2
inH2O @ 39ºF
inH2O @ 60ºF
inH2O @ 68ºF
inHg @ 0ºC
kgf/cm2, kPa
mbar,
mmH2O @ 4ºC,
mmH2O @ 68ºF,
mmHg @ 0ºC,
MPa, Pa,
psi
Torr,
mH2O @ 4ºC
mHg @ 0ºC
Do Correct
Do Correct
Do Correct
Do Correct
DAC Zero Trim
DAC Span Trim
Loop Test
12.000
ST 700 SmartLine Pressure Transmitters User's Manual
Choose appropriate engineering
units from list
Executing this selection corrects the
Zero based on the input pressure
Executing this selection corrects the
LRV based on the input pressure
Executing this selection corrects the
LRV based on the input pressure
Executing this selection Resets the
Zero, LRV, and URV Corrects back
to Factory values
This selection allows the loop zero
output 4mA value to be trimmed.
Note: You must connect a current
meter to the transmitter to monitor
the loop output.
This selection allows the loop span
output 20mA value to be trimmed.
Note: You must connect a current
meter to the transmitter to monitor
the loop output.
This selection allows the user to
force the DAC output to any value
between 3.8 and 20.8 mA.
Note: This selection will put the DAC
into Fixed Output Mode, as
indicated by the flashing output
value. Navigation away from this
menu item will return the loop to
Normal (Automatic) Mode.
↵ to enter
Press ↵ to
enter menu
selection
Press ↵ to
initiate action
Press ↵ to
enter menu
selection
↑ and ↓ to
select
number.
↵ to enter
and shift to
the next digit
to the right
Revision 1.0