3.4.3 Bracket Mounting Procedure
If you are using an optional bracket, start with Step 1. For an existing bracket, start with Step 2.
1. Refer to Figure 5. Position the bracket on a 2-inch (50.8 mm) horizontal or vertical pipe, and
install a "U" bolt around the pipe and through the holes in the bracket. Secure the bracket
with the nuts and lock washers provided.
Mounting
Bracket
Horizontal Pipe
Figure 5 – Angle Mounting Bracket Secured to a Horizontal or Vertical Pipe
2. Align the appropriate mounting holes in the Transmitter with the holes in the bracket. Use the
bolts and washers provided to secure the Transmitter to the bracket; see the following
variations.
Transmitter Type
DP with double-ended process heads
and/or remote seals
In-line GP and AP (STGxxL and
STAxxL)
Dual-head GP and AP
EXAMPLE: Inline model mounted to an optional angle bracket. See Figure 6.
Revision 2.0
Nuts and
Lockwashers
U-Bolt
Table 4 Mounting Bracket procedure
ST 700 Smart Pressure Transmitter User's Manual
U-Bolt
Vertical Pipe
Use Hardware
Alternate mounting holes in the ends of the
heads
The smaller "U" bolt provided to attach the
meter body to the bracket. See the
following example.
Mounting holes in the end of the process
head.
Nuts and
Lockwashers
Mounting
Bracket
Page 9