Table 1.6 Primequest 480 Main Unit Installation Specifications (Model Name: Mc5A0P1A1X) - Fujitsu PRIMEQUEST 580A Installation Planning Manual

Hide thumbs Also See for PRIMEQUEST 580A:
Table of Contents

Advertisement

CHAPTER 1 Installation Reference
Table 1.6 PRIMEQUEST 480 main unit installation specifications
Dimensions
Width
[mm (in.)]
Depth (*1)
Height
Weight [kg (lb)] (*2)
Air conditioning Maximum heat dissipation
(*9)
[kJ/Hr (BTU/h)]
Exhaust air flow
3
[m
Temperature
and humidity
(*3)
Noise [dB (A)] (*6) (*9)
Sound power level [B (A)] (*6) (*9)
Allowable
vibration
[m/s
Allowable dust [mg/m
Power supply
Input voltage tolerance and No. of phases
Frequency and tolerance
1-22
(Model name: MC5A0P1a1x)
Item
3
/min (ft
/min)]
Operating
Stand-by
Not operating
(*5)
Operating (including standby)
2
Not operating (*5)
]
3
]
Five SBs or five IO
Units or more
Four SBs or less and
four IO Units or less
With fans operating at
low speed
With fans operating at
high speed
Temperature [°C (°F)] (*4)
Humidity [%RH]
Maximum wet bulb
temperature [°C (°F)]
Temperature [°C (°F)] 0 to 40 (32 to 104)
Humidity [%RH]
Maximum wet bulb
temperature [°C (°F)]
Temperature [°C (°F)] 0 to 50 (32 to 122)
Humidity [%RH]
Maximum wet bulb
temperature [°C (°F)]
Value
738 (29.06)
1100 (43.31)
1800 (70.87)
720 (1584)
36600 (34689)
20500 (19430)
49.1 (1733.9)
62.2 (2196.6)
20 to 80
26 (78.8)
20 to 80
26 (78.8)
8 to 80
27 (80.6)
66
8.5
2.5 (Synthetic
seismic vibration)
4.0 (Synthetic
seismic vibration)
0.15
200 to 240 VAC ± 10 %
50/60 Hz +2/-4 Hz
U41631-J-Z816-5-76