4. Wiring Terminal Block
You can remove the cover to perform the connection.
-
Terminal: Positive(+), negative(-) and neutral (N).
-
-
Two blocks for connecting the UPS and the next battery cabinet.
Note:
For longer autonomy times you can connect up to 4 battery cabinets in
parallel. If you use only one battery cabinet the maximum UPS power for
one 1165 mm cabinet is 40kVA, for one 1665mm is 60kVA.
Fig. 3-6 Rear View of Battery Cabinet 1165mm height