Environmental Specifications - Cisco 6000 Series Site Planning Manual

Network convergence system routers
Hide thumbs Also See for 6000 Series:
Table of Contents

Advertisement

Chapter 3
System Specifications
Table 3-2
AC Input
Nominal input voltage
Nominal line frequency
Recommended AC service
AC Power Cord Length

Environmental Specifications

Table 3-3
Temperature
Humidity
Altitude
Chassis airflow
Power system airflow
Air exhaust temperature 140°F (60°C)—at room temperatures of 95 to 102°F (35 to 39°C)
Air velocity
(at exhaust)
Sound power level
(AC and DC power)
Shock and vibration
1. Short-term refers to a period of not more than 96 consecutive hours and a total of not more than 15 days in 1 year. This refers
OL-29236-02
Cisco NCS 6008 Chassis Power Specifications (continued)
Cisco NCS 6008 Chassis Environmental Specifications
Operating, nominal: 41 to 104°F (5° to 40°C)
Operating, short-term: 23 to 122°F (–5° to 50°C)
Nonoperating: –40 to 158°F (–40° to 70°C)
Operating, nominal: 5 to 85%, noncondensing
Operating, short-term: 5 to 90%, noncondensing
Nonoperating: 5 to 93%, noncondensing
Operating: –200 to 13,800 ft (–61 to 4206 m) at 104°F (40°C)
Nonoperating: Up to 16,000 ft (4877 m) at –13°F (–25°C), short-term
Up to 70,792 liters per minute
Up to 6800 liters per minute
158°F (70°C)—maximum exhaust temperature on a fully loaded system
during worst-case operating conditions (50°C and 6000 ft altitude)
Note
1000 ft/min (5.1m/s) under typical conditions 27°C
2250 ft/min(11.4m/s) at maximum speed
Note
Fan speed 3500 RPM, temperature 80°F (27°C):
77.2 dB—modular configuration power
Designed and tested to meet the NEBS shock and vibration standards defined
in GR-63 Issue 4 2012.
to a total of 360 hours in any given year, but no more than 15 occurrences during that 1-year period.
Cisco Network Convergence System 6000 Series Routers Site Planning Guide
Single-phase
200 to 240 VAC (range 180 to 264 VAC)
50/60 Hz (range 47 to 63 Hz)
20-A (North America) dedicated branch circuit
16-A (International) dedicated branch circuit
167 in. (4.25 m)
Air temperature rise is 68°F (20°C) on a fully loaded system with
fans running at maximum speed.
Software controls the speed of the fans based on measurements from
the chassis thermal sensors.
Environmental Specifications
1
3-3