Honeywell TB7200 Integration Manual page 23

Tb7200 & tb7300 series bacnet thermostats with occupancy sensor
Table of Contents

Advertisement

Enumeration Sets for MV Objects
Object Name
Sequence of
Operation
System Mode
Note 1
Fan Mode
Note 3
Occupancy
Command
Keypad Lockout
NOTES:
1.
Enumeration sets for MV16 depends on Sequence of Operation (MV15) value upon device discovery. If required
enumeration is not present, set MV15 to desired value and rediscover MV16 object. Available enumeration will now
reflect required configuration.
2.
Default value of MV16 depends on MV15 value upon device discovery.
MV15 Index
Function
1
Cooling Only
2
Cooling with Reheat
3
Heating Only
4
Heating with Reheat
5
Cooling/Heating 4 Pipes
6
Cooling/Heating 4 Pipes with Reheat
3.
Enumeration sets for MV17 depends on Fan Mode Sequence (MV58) value upon device discovery. If required enu-
meration is not present, set MV58 to desired value and rediscover MV17 object. Available enumeration will now
reflect required configuration.
4.
Available state text and default value depends on Fan Mode Sequence (MV58) value upon device discovery.
5.
Same as Note 4.
BACNET INTEGRATION MANUAL FOR TB7200 & TB7300 SERIES THERMOSTATS
Table 10. Property enumeration sets for MV objects.
Object ID
BACnet Index
1
2
3
MV 15
4
5
6
1
2
MV 16
3
4
MV 17
1, 2, 3 or 4
1
MV 18
2
3
1
2
3
MV 19
4
5
6
Text
Cooling Only
Heating Only
Cooling & Reheat
Heating & Reheat
Cool/Heat4P
Cool/Heat4P&Reht
Off
Auto
Cool
Heat
Note 4
Local Occupancy
Occupied
Unoccupied
Level 0
Level 1
Level 2
Level 3
Level 4
Level 5
Default Value is BV50
Enabled
Cool
Auto
Heat
Heat
Auto
Auto
23
Default value
Heating Only
Note 2
Note 5
Depends on network
command
Level 0
Default Value is BV50
Disabled
Cool
Heat
Heat
Heat
Heat
Heat
63-4524—02