Honeywell TB7200 Integration Manual page 11

Tb7200 & tb7300 series bacnet thermostats with occupancy sensor
Table of Contents

Advertisement

BACNET INTEGRATION MANUAL FOR TB7200 & TB7300 SERIES THERMOSTATS
TB7300 Integration – Graphical User Interface (GUI) Objects
The following objects should be typically used in a GUI:
• Room Temperature (AV7);
• Occupied and Unoccupied Heat Setpoints (AV 39 and AV43);
• Occupied and Unoccupied Cool Setpoints (AV 40 and AV34);
• Room Humidity (AV10) (If available);
• Room Humidity Setpoint (AV 71) (If available);
• Outdoor Temperature (AV 9);
• Supply Temperature (AI12) (If available);
• Occupancy Command (MV18);
• System Mode (MV16);
• Fan Mode (MV17);
• Fan Status (MV28);
• Heating Valve Status (MV26);
• Cooling Valve Status (MV28);
• PI Heating Demand (AV21);
• PI Cooling Demand (AV22);
• Window Alarm (BI 35);
• Filter Alarm (BI 36);
• Service Alarm (BI 37)
Fig. 8. Example of graphical user interface objects.
11