Honeywell TB7200 Integration Manual page 21

Tb7200 & tb7300 series bacnet thermostats with occupancy sensor
Table of Contents

Advertisement

Property Value Range Restrictions
Object name
Room Temperature
Outdoor Temperature
Room Humidity
Supply Temperature
PI Heating demand
PI Cooling demand
Occupied Heat Setpoint
Occupied Cool Setpoint
Stand-by Heat Setpoint
Stand-by Cool Setpoint
Unoccupied Heat Setpoint
Unoccupied Cool Setpoint
Password Value
Heating Setpoint Limit
Cooling Setpoint Limit
Deadband
Stand-by Time
Unoccupied Time
RH Setpoint
Dehumidification Hysterisys
Dehumidification MAX cooling
BACNET INTEGRATION MANUAL FOR TB7200 & TB7300 SERIES THERMOSTATS
Table 8. Property value range restrictions.
Object Type
Minimum range
and instance
value
AV 7
-39.9°F (-40°C)
AV 9
-39°F (-40°C)
AV 10
5%
AI 12
-39.9°F (-40°C)
AV 21
0%
AV 22
0%
AV 39
40°F (4.5°C)
AV 40
54°F (12°C)
AV 41
40°F (4.5°C)
AV 42
54°F (12°C)
AV 43
40°F (4.5°C)
AV 44
54°F (12°C)
AV 56
AV 58
40°F (4.5°C)
AV 59
54°F (12°C)
AV 63
2°F (1°C)
AV 67
0.5 Hours
AV 68
0.0 Hours
AV 45
30%
AV 46
2%
AV 47
20%
21
Maximum
range value
121.9°F (50°C)
121.9°F (50°C)
90%
121.9°F (50°C)
100%
100%
90°F (32°C)
100°F (37.5°C)
90°F (32°C)
100°F (37.5°C)
90°F (32°C)
100°F (37.5°C)
0
1000
90°F (32°C)
100°F (37.5°C)
5°F (2.5°C)
24.0 Hours
24.0 Hours
100%
20%
100%
Default value
N/A
N/A
N/A
N/A
0%
0%
72°F (22°C)
74°F (24°C)
72°F (22°C)
74°F (24°C)
62°F (16.5°C)
80°F (26.5°C)
0
90°F (32°C)
54°F (12°C)
2°F (1°C)
0.5 Hours
0.0 Hours
50%
5%
100%
63-4524—02