Property Value Range Restrictions
Object name
Room Temperature
Outdoor Temperature
Room Humidity
Supply Temperature
PI Heating demand
PI Cooling demand
Occupied Heat Setpoint
Occupied Cool Setpoint
Stand-by Heat Setpoint
Stand-by Cool Setpoint
Unoccupied Heat Setpoint
Unoccupied Cool Setpoint
Password Value
Heating Setpoint Limit
Cooling Setpoint Limit
Deadband
Stand-by Time
Unoccupied Time
RH Setpoint
Dehumidification Hysterisys
Dehumidification MAX cooling
BACNET INTEGRATION MANUAL FOR TB7200 & TB7300 SERIES THERMOSTATS
Table 8. Property value range restrictions.
Object Type
Minimum range
and instance
value
AV 7
-39.9°F (-40°C)
AV 9
-39°F (-40°C)
AV 10
5%
AI 12
-39.9°F (-40°C)
AV 21
0%
AV 22
0%
AV 39
40°F (4.5°C)
AV 40
54°F (12°C)
AV 41
40°F (4.5°C)
AV 42
54°F (12°C)
AV 43
40°F (4.5°C)
AV 44
54°F (12°C)
AV 56
AV 58
40°F (4.5°C)
AV 59
54°F (12°C)
AV 63
2°F (1°C)
AV 67
0.5 Hours
AV 68
0.0 Hours
AV 45
30%
AV 46
2%
AV 47
20%
21
Maximum
range value
121.9°F (50°C)
121.9°F (50°C)
90%
121.9°F (50°C)
100%
100%
90°F (32°C)
100°F (37.5°C)
90°F (32°C)
100°F (37.5°C)
90°F (32°C)
100°F (37.5°C)
0
1000
90°F (32°C)
100°F (37.5°C)
5°F (2.5°C)
24.0 Hours
24.0 Hours
100%
20%
100%
Default value
N/A
N/A
N/A
N/A
0%
0%
72°F (22°C)
74°F (24°C)
72°F (22°C)
74°F (24°C)
62°F (16.5°C)
80°F (26.5°C)
0
90°F (32°C)
54°F (12°C)
2°F (1°C)
0.5 Hours
0.0 Hours
50%
5%
100%
63-4524—02