InSTalleR SeTuP

FocusPRO
5000 Series
®
1.
To begin, press and hold the s and FAN buttons until
the display changes.
2.
Press s or t to change settings.
Function
Setting
1
0
Done
Next
3.
Press NEXT to advance to the next function.
4.
Press DONE to exit and save settings.
5.
Proceed to Installer Setup Functions on page 4.
2
FocusPRO
6000 Series
®
1.
To begin, press and hold the s and FAN buttons until
the display changes.
2.
Press s or t to change settings.
Function
Setting
1
0
Done
Next
3.
Press NEXT to advance to the next function.
4.
Press DONE to exit and save settings.
5.
Proceed to Installer Setup Functions on page 4.
3

InSTalleR SeTuP FuncTIOnS

Available option and default settings vary by thermostat.
Table 1. Installer Setup
Setup functions
Setting & Options
(factory default in bold)
1
System type
0
1 heat / 1 cool Conv.
1
1 heat / 1 cool heat
pump (no Aux. heat)
2
Heat only (2-wire, 3-wire
zone valves [Series 20],
and normally open zone
valves)
3
Heat only with fan
4
Cool only
5
2 heat / 1 cool heat
pump (with Aux. heat)
6
2 heat / 2 cool Conv.
7
2 heat / 1 cool Conv.
8
1 heat / 2 cool Conv.
9
2 heat / 2 cool heat pump
(no Aux. heat)
10
3 heat / 2 cool heat
pump (with Aux. heat)
2
Changeover valve
0
Controls valve in cooling
(O/B terminal)
1
Controls valve in heating
3
Fan control
0
Gas/Oil heat (equipment
(heating)
controls heating fan)
1
Electric furnace (thermo-
stat controls heating fan)
5
First stage heat
5
Gas or oil furnaces of
cycle rate
less than 90%
efficiency
1
Steam or gravity
3
Hot water systems or fur-
naces of 90%+ efficiency
9
Electric furnaces
[Other options: 1–12]
6
Second stage
5
Gas or oil furnaces of
heat/Aux heat
less than 90% efficiency
cycle rate
1
Steam or gravity
3
Hot water systems or fur-
naces of 90%+ efficiency
9
Electric furnaces
[Other options: 1–12]
7
Auxiliary heat
5
Gas or oil furnaces of
cycle rate
less than 90% efficiency
1
Steam or gravity
3
Hot water systems or fur-
naces of 90%+ efficiency
9
Electric furnaces
[Other options: 1–12]
4
Table 1. Installer Setup
Setup functions
Setting & Options
(factory default in bold)
8
Emergency heat
9
Electric emergency heat
cycle rate
1
Steam or gravity
3
Hot water systems or fur-
naces of 90%+ efficiency
5
Gas or oil furnaces of
less than 90% efficiency
[Other options: 1–12]
9
First stage
3
Recommended
compressor cycle
[Other options: 1–6]
rate
10
Second stage
3
Recommended
compressor cycle
[Other options: 1–6]
rate
12
Manual/Auto
0
Manual changeover
changeover
(Heat/Cool/Off)
1
Auto changeover (Heat/
Cool/Auto/Off)
2
Auto changeover only
(Auto)
13
Adaptive Intel-
1
On
ligent Recovery
0
Off
TM
14
Temperature
0
Fahrenheit
display
1
Celsius
15
Compressor
5
5-minute compressor
protection
off time
[Other options: 0–4
minutes]
16
Schedule format
0
5/2 (weekdays
and weekends
programmable)
1
5/1/1 (weekdays,
Saturday, and Sunday
programmable)
26
Auxiliary heat
0
Comfort
control
1
Economy
27
Heat temperature
90
Max. heat temperature
range stops
setting is 90°F (32°C)
[Other options: 40–89°F
(4.5°C to 32°C)]
28
Cool temperature
50
Min. cool temperature
range stop
setting is 50°F (10°C)
[Other options: 51–99°F
(10.5°C to 37°C)]
Functions 13 and 16 only available on the 6000 series;
function 26 only available on the 5000 series
5
Printed in U.S.A. on recycled
paper containing at least 10%
post-consumer paper fibers.
Automation and Control Solutions
Honeywell International Inc.
1985 Douglas Drive North
Golden Valley, MN 55422
Honeywell Limited-Honeywell Limitée
35 Dynamic Drive
Toronto, Ontario M1V 4Z9
http://yourhome.honeywell.com
® U.S. Registered Trademark
© 2006 Honeywell International Inc.
US Patent No. 6595430, D509151; other
Patents Pending. All Rights Reserved
69-2026 M.S. 09-06

Hide quick links:

Advertisement

loading

This manual is also suitable for:

Focuspro 6000 series