Tp970 and tp9600 series pneumatic thermostats
Hide thumbs Also See for B:
Table of Contents

Advertisement

15
(100)
14
(90)
13
12
(80)
11
(70)
10
9
(60)
8
TP970D MAXIMUM
(50)
7
THROTTLING
6
(40)
RANGE = 20F (11.1C)
5
(30)
4
(20)
3
2
(10)
12.5
10
7.5
5
2.5
1
15
0
(8) (7) (6) (5) (4) (3) (2) (1)
BELOW SETPOINT
DEVIATION IN SPACE TEMPERATURE—DEGREES F (C)
Fig. 3. TP970D Space Temperature Vs Branchline
Pressure.
M B
M
HEATING
VALVE
2 TO 5 PSI
(14 TO 34 kPa)
SPRING
N.O.
VALVE
OPEN
4 DEGREES F
(2.2 DEGREES C)
ZERO
ENERGY
BAND
VALVE
CLOSED
66F
68F
70F
20C
THERMOSTAT SETTING
TR=10 DEGREES F
(5.6 DEGREES C)
Fig. 4. Typical TP970C Operation Using Selected Spring
Range Valve Operators.
TP970C
DIRECT
ACTING
M B
M
RP971A—3 PSI
2
SPAN—SET
3
1
3.9 PSI (26.9 kPa)
4
START
EXH
M
HEATING
N.O.
VALVE
3 TO 10 PSI
(21 TO 68.9 kPa)
VALVE
OPEN
4 DEGREES F
(2.2 DEGREES C)
VALVE
CLOSED
66F
68F
70F
20C
THERMOSTAT SETTING
TR=10 DEGREES F
(5.6 DEGREES C)
Fig. 5. Typical TP970C Operation Using Ratio Relays.
TP970D MINIMUM
THROTTLING RANGE =
5F (2.8C)
SETPOINT
2.5
5
7.5
10
12.5
(1)
(2)
(3)
(4)
(5)
(6)
(7)
(8)
SETPOINT
ABOVE SETPOINT
C3537
TP970C
DIRECT
ACTING
COOLING
VALVE
9 TO 13 PSI
(62 TO 90 kPa)
SPRING
N.C.
72F
74F
76F
78F
24C
22C
C3538
RP971A—3 PSI
2
RANGE—SET
3
1
10 PSI (68.9 kPa)
4
START
EXH
M
COOLING
N.C.
VALVE
3 TO 10 PSI
(21 TO 68.9 kPa)
ZERO
ENERGY
BAND
72F
74F
76F
78F
24C
22C
C3539
TP970 AND TP9600 SERIES PNEUMATIC THERMOSTATS
TP971A, B, D, E and TP9610A,B
These thermostats provide a BLP proportional to the ambient
temperature. In a heating application with a normally open
valve (Fig. 6), a fall in room temperature causes the
thermostat to lower the BLP to the valve, providing a
proportional action matching the existing load requirement.
When the supply air pressure is 13 psi (90 kPa), the
thermostat controls at the normal DAY setting. When the
15
supply air is switched to 18 psi (124 kPa), the thermostat
controls at the reduced NITE setting. Models with 16 or 21 psi
(110 or 145 kPa) pressure are available. The TP971D is the
same as the TP971A with the addition of NITE setup. The
TP971E is the same as the TP971B with the addition of NITE
setup.
The manual reset lever protrudes through the DAY/AUTO slot
in the cover. The lever is used to manually reset the
thermostat from AUTO to DAY to restore day operation. The
lever automatically returns to the AUTO position when the
supply air reaches DAY pressure.
DAY
13 PSI
(90 kPa)
M
NITE
18 PSI
(124 kPa)
Fig. 6. TP971A and TP9610A Typical Operation.
TP971C
The TP971C can be used with a unit ventilator to control a
heating valve, outdoor- and return-air dampers, and blower
motor (Fig. 7). When supply air pressure is 13 psi (90 kPa),
the TP971C controls the valve and damper at the normal DAY
setpoint. When supply air pressure is 18 psi (125 kPa), the
TP971C closes the outdoor-air damper and switches the
blower from constant to automatic operation. The TP971C
then cycles the unit at reduced night setpoint. Models with 18
or 21 psi (125 or 145 kPa) pressure are available.
The manual reset lever protrudes through the DAY/AUTO slot
in the cover. The lever may be used to manually reset the
TP971C from AUTO to DAY to restore DAY operation,
including outdoor-air damper operation. The reset lever
automatically returns to the AUTO position when the supply
air reaches DAY pressure.
9
TP971A OR
TP9610A
M B
N.O.
HOT WATER
OR STEAM
C3540-1
SUPPLY
75-7134—1