Honeywell B Service Data page 17

Tp970 and tp9600 series pneumatic thermostats
Hide thumbs Also See for B:
Table of Contents

Advertisement

Day/Auto Lever Assembly Replacement
1. Remove the three Phillips head screws that fasten the
lever mechanism to the back of the thermostat (Fig.
20).
2. Lift off the cover plate and remove the lever (with
attached seal).
3. Lift the spring from the post.
4. Install the replacement parts in reverse order.
5. Replace and tighten screws.
SPRING
LEVER
COVER
PLATE
Fig. 20. DAY/AUTO Lever Assembly Replacement.
TP970 AND TP9600 SERIES PNEUMATIC THERMOSTATS
CAUTION:
THIS PIN IS FREE
TO DROP OUT WHEN
LEVER IS RELEASED.
M12205
17
Switchover Adjustment Spring Replacement
1. Using a screwdriver, carefully remove the screw and
switchover adjustment spring (Fig. 21). See PARTS
LIST in PARTS and ACCESSORIES section for
available springs.
2. Replace the spring, then carefully position and replace
the screw.
3. Calibrate the thermostat.
14001992-001
16/21 PSI
CHANGEOVER
SPRING
SCREW
Fig. 21. Switchover Adjustment Spring Replacement.
M12137
75-7134—1

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents