Honeywell C7150B Product Data page 9

Solid state economizer system
Hide thumbs Also See for C7150B:
Table of Contents

Advertisement

To mount the C7046C Sensor in a junction box (see Fig. 11):
1. Cut a 1/2 in. (13 mm) hole in the duct or plenum surface
at the desired location.
2. Remove the center rear knockout from the junction box
and insert the sensor probe through the knockout with
the flange flat against the junction box.
3. Using the flange as a template, mark and drill two holes
in the junction box and the duct or plenum surface for no.
8 mounting screws.
4. Insert the sensor probe through both the junction box
knockout and the 1/2 in. (13 mm) hole drilled in the duct
or plenum and fasten the junction box and sensor to the
duct or plenum surface with the two no. 8 sheet metal
screws (not provided).
CONNECTOR
AND
LOCKNUT
M9088
Fig. 11. Mounting C7046C Discharge Air Temperature Sensor in junction box.
Wiring
CAUTION
Can Cause Electrical Shock or Equipment Damage.
Disconnect the power supply before connecting the
wiring.
Make sure wiring complies with applicable local codes,
ordinances and regulations.
TO APPROPRIATE
SYSTEM COMPONENTS
(SEE WIRING DIAGRAM)
SYSTEM DUCT OR PLENUM
9
SENSOR PROBE
TO APPROPRIATE
SYSTEM COMPONENTS
(SEE WIRING DIAGRAM)
1
Fig. 10. Mounting C7046C Air Temperature Sensor on duct
STANDARD 2 X 4 (51 X 102)
OUTLET BOX (OPTIONAL)
SENSOR PROBE
FLANGE
1
SENSOR WIRES WITH 2
SOLDERLESS CONNECTORS
1
SCREWS NOT PROVIDED.
Connect low voltage wiring from the sensor to the appropriate
system component terminals using solderless connectors as
shown in Fig. 10 and 11.
SOLID STATE ECONOMIZER SYSTEM
SYSTEM DUCT OR PLENUM
FLANGE
SENSOR WIRES WITH
2 SOLDERLESS
CONNECTORS
SCREWS NOT PROVIDED.
or plenum.
BLANK
FACEPLATE
(OPTIONAL)
NO. 8
MOUNTING
SCREWS (2)
1
M9086
63-2484—2