Download Print this page

Honeywell F118 Specification Data

In-ceiling media air cleaner
Hide thumbs Also See for F118:

Advertisement

Quick Links

APPLICATION
The F118 media air cleaner uses a three-speed direct-drive forward-
curve blower motor and a 95 percent D.O.P. particle filter to capture
airborne particles such as dust, soot, and cooking smoke from the
circulating air. When equipped with two CPZ™ modules, the air
cleaner also adsorbs gases and odors from the air passing through it.
The F118 is recommended for use in rooms with drop ceilings, and for
spaces with structural ceilings not higher than 16 ft (4.8m), where
there is a minimum one ft (0.3m) clearance between the drop ceiling
and the structural ceiling.
The F118 media air cleaner uses the Coanda effect to circulate air
through the space. This effect is the tendency of air to travel close to a
wall contour when ejected from a jet. The air cleaner draws
contaminated air up from the center of the room, forces it through the
filters, and blows the filtered air out through both narrow ends of the air
cleaner.

SPECIFICATIONS

IMPORTANT
The specifications given in this publication do not include
normal manufacturing tolerances. This unit might not exactly
match the listed specifications. Also, this product is tested
and calibrated under closely controlled conditions, and some
minor differences in performance can be expected if those
conditions change.
Table 1. Air Volume
Air
Cubic
Cubic
Volume
ft./Min.
Meters/Hr.
High
425 cfm
723 m
Medium
300 cfm
510 m
Low
200 cfm
340 m
Color:
Galvanized steel cabinet and white cover.
The Honeywell Trademark is used under license from Honeywell
Intellectual Properties, Inc. by Air-Pure Systems.
Honeywell International Inc. makes no representations or
warranties with respect to this product.
In-Ceiling Media Air Cleaner
Current
Sound level
Draw
at 3.3 ft (1m)
3
/hr
2.8A
65 dBA
3
/hr
2.0A
54.5 dBA
3
/hr
1.4A
48 dBA
FEATURES
D.O.P. particle filter is 95 percent efficient at 0.3 micron par-
ticles, and more efficient on both larger and smaller particles.
CPZ™ modules can reduce space odors.
3
Circulates air up to 425 ft
Provides Coanda air distribution by drawing in dirty air,
cleaning it, and bi-directionally recirculating the filtered air
throughout the space.
Designed to overcome the increase in air flow resistance
normally caused by filter loading.
White cover compliments ceiling color.
Accessible three speed push-button switch.
Optional wall-mounted remote switch.
Easy to remove and replace filters.
Blower/Motor:
Three-speed direct-drive forward curve. Motor lubrication is not
required.
Ambient Temperature Rating:
o
Shipping and Storage: -20
F to +150
Operating: This equipment is intended for use at ambient
temperatures that usually are not higher than 77
occasionally can be as high as 104
time. It functions in an environment of up to 95 percent relative
humidity, non-condensing.
Electrical Ratings:
120V, 60 Hz.
Grille Type:
Perforated metal.
23-1/2
(597)
12-1/2
(317)
1 (25) CLEARANCE
OF DROP CEILING
POWER CONNECTOR
(ELECTRICAL BOX)
SUPPORT RODS
M16213
PRE-FILTER (WRAPS)
Fig. 1. Approximate dimensions of F118 in inches (mm).
F118
SPECIFICATION DATA
3
/minute (723m
/hour).
o
o
o
F (-29
C to +66
C).
F (25
C), but
o
o
F (40
C) for brief periods of
o
o
47-3/4
(1213)
VIEW UNDERSIDE
(GRILL REMOVED)
PARTICULATE FILTER
68-3029-2 Revised 11-07

Advertisement

loading

Summary of Contents for Honeywell F118

  • Page 1: Specifications

    When equipped with two CPZ™ modules, the air cleaner also adsorbs gases and odors from the air passing through it. The F118 is recommended for use in rooms with drop ceilings, and for spaces with structural ceilings not higher than 16 ft (4.8m), where there is a minimum one ft (0.3m) clearance between the drop ceiling...
  • Page 2 NOTE: Qty in (#) is required qty per unit. Air-Pure Systems 16873 Fish Point Rd. SE Prior Lake, MN 55372-1714 Phone: (800) 998-1010 Fax: (800) 221-3248 68-3029—1 68-3029-2 Revised 11-07 Fig. 9. F118 Air Cleaner components www.cleanairfacility.com M16205...