W180 ZONE CONTROL SYSTEM
Function
Anticipation
For heating equipment. A value greater than 1
—Heat
increases the equipment cycle rate; a value less
than 1 decreases the equipment cycle rate.
Recommended values:
—Electric: 1.5.
—Forced Air: 1.2.
—Heat Pump: 1.0.
—Hydronic/Radiant: 0.8.
Anticipation
For cooling equipment. A value greater than 1
—Cool
increases the equipment cycle rate; a value less
than 1 decreases the equipment cycle rate.
Recommended values:
—Cooling Compressor: 1.0.
Overrun
The length of time in minutes the fan defined
Time—Heat
for this stage is active following a call for
heating.
Overrun
The length of time in minutes the fan defined
Time—Cool
for this stage is active following a call for
cooling.
Minimum Off
The length of time in minutes that must expire
Time—Heat
following a call for heating before the stage
equipment may be activated again.
Minimum Off
The length of time in minutes that must expire
Time—Cool
following a call for cooling before the stage
equipment may be activated again.
Lockout
When the outdoor temperature is above this
Temperature
temperature, the stage is locked out.
—Heat
Lockout
When the outdoor temperature is below this
Temperature
temperature, the stage is locked out.
—Cool
Outside Temp
When the actual outdoor temperature is below
for Alt. Eq.—
this value, any heating equipment set up during
Heat
configuration as Alt. Eq.—Heat will be
activated in place of the equipment defined as
Normal—Heat.
Outside Temp
When the actual outdoor temperature is above
for Alt. Eq.—
this value, any cooling equipment set up during
Cool
configuration as Alt. Eq.—Cool will be
activated in place of the equipment defined as
Normal—Cool.
Stage
The number of degrees below setpoint the
Differential—
average zone demand must exceed before this
Heat
stage is activated.
Stage
The number of degrees above setpoint the
Differential—
average zone demand must exceed before this
Cool
stage is activated.
Stage
Use this equipment during manual system
Attributes—
override to Emergency Heat mode in place of
Emergency
the first stage heat pump equipment in heating.
Heat
68-0139
HVAC CONFIGURATION TABLE (Continued).
Definition
18
Minimum
Maximum
0.0
1.5
0.0
1.5
0
30
0
30
3
30
3
30
10 F
99 F
10 F
99 F
10 F
99 F
10 F
99 F
1st Stage: 0 F
1st Stage: 20 F
2nd Stage: 1st Stage
2nd Stage: 20 F
+ 1 F
3rd Stage: 20 F
3rd Stage: 2nd Stage
+ 1 F
1st Stage: 0 F
1st Stage: 20 F
2nd Stage: 1st Stage
2nd Stage: 20 F
+ 1 F (1 F)
3rd Stage: 20 F
3rd Stage: 2nd Stage
+ 1 F (2 F)
Default
1.0
1.0
2
2
3
3
90 F
50 F
40 F
90 F
1st Stage: 0 F
2nd Stage: 4 F
3rd Stage: 6 F
1st Stage: 0 F
2nd Stage: 4 F
3rd Stage: 6 F