T7771A REMOTE TEMPERATURE SENSOR
Averaging Multiple Sensors
The default position for the J2 jumper is 20K ohms. When
using a single sensor, leave the jumper in this position.
For temperature averaging using a T7350 Commercial
Thermostat and multiple sensors, use the following
guidelines:
— Only one T7771 can be used.
— For the second sensor, use a T7770A3002 (which has a
10K ohm output).
— Wire the two sensors in series.
9
8
7
6
5
4
3
2
1
Fig. 6. Wiring diagram for T7771A Wall Modules.
T7350 SUBBASE
T4
T3
T7770A3002
T7771A
T4
T3
T4
1
APPROPRIATE T7771A JUMPER POSITION
FOR TWO SENSOR TEMPERATURE AVERAGING.
Fig. 7. Temperature averaging with two sensors.
Automation and Control Solutions
Honeywell International Inc.
Honeywell Limited-Honeywell Limitée
1985 Douglas Drive North
35 Dynamic Drive
Golden Valley, MN 55422
Scarborough, Ontario
M1V 4Z9
63-2617
B.B. 6-04
20K OHM OUTPUT
J2
10K OHM OUTPUT
J2
M22175
1
10K OHM
OUTPUT
T3
J2
J2
M22280
T7350 SUBBASE
T4
T7770A1006
T4
T3
T7770A1006
T4
T3
1
APPROPRIATE T7771A JUMPER POSITION
FOR FOUR SENSOR TEMPERATURE AVERAGING.
Fig. 8. Temperature averaging with four sensors.
1.
STRIP 1/2 IN.
1/2
(13 MM) FROM
(13)
WIRES TO BE
ATTACHED AT
ONE TERMINAL.
2.
TWIST WIRES
TOGETHER
WITH PLIERS
(A MINIMUM OF
THREE TURNS).
Fig. 9. Attaching two wires at wall module terminals.
When all wiring is complete, attach the cover of the T7771A
Wall Module by reversing step 2 of Fig. 2.
ACS Control Products
Honeywell AG
Böblinger Straße 17
D-71101 Schönaich
Phone (49-7041) 637-01
Fax (49-7041) 637-493
T3
1
T7771A
20K OHM
T4
T3
OUTPUT
J2
J2
T7770A1006
T4
T3
M22281
CONTROLLER OR
WALL MODULE
E-BUS CONNECTOR
TERMINALS
3.
CUT TWISTED END OF WIRES TO
3/16 IN. (5 MM) BEFORE INSERTING
INTO TERMINAL AND TIGHTENING
SCREW. THEN PULL ON EACH WIRE
IN ALL TERMINALS TO CHECK FOR
GOOD MECHANICAL CONNECTION.