Download Print this page

Specifications; Ordering Information - Honeywell C6097A Product Data

Pressure switches

Advertisement

C6097A,B PRESSURE SWITCHES

SPECIFICATIONS

Models:
C6097A Pressure Switch: Breaks a circuit when pressure falls
to scale setting. See Table 1.
C6097B Pressure Switch: Breaks a circuit when pressure
rises to scale setting. See Table 1.
Table 2 shows switch ratings and Table 3 shows alternate
electrical ratings when used with Honeywell Flame Safeguard
Programmers.
Minimum Ambient Temperature: -40°F (-40°C).
Maximum Ambient Temperature: 140°F (60°C).
Connections (Depending on Model):
1/4-18 NPT tapping for main or high-pressure connection.
1/8-27 NPT tapping for vent or low-pressure connection (air
only).
Flange mount for connection to Honeywell Integrated Valve
Train (internal vent only, no external connections).
Scale Range:
0.4 to 5 in. wc (0.10 kPa to 1.25 kPa).
3 to 21 in. wc (0.75 to 5.23 kPa).
12 to 60 in. wc (3.0 kPa to 15 kPa).
1.5 to 7 psi (10.3 kPa to 48 kPa).
Approvals:
Underwriters Laboratories Inc. listed.
Canadian Standards Association listed.
Factory Mutual: Approved.
Industrial Risk Insurers: Acceptable.
CSD-1 AFB: Acceptable.
Accessories:
32003041-001 C6097 Cover for manual reset models.
32003040-001 C6097 Cover for recycle models.
32003039-001 Position Indication Lamp Kit.

ORDERING INFORMATION

When purchasing replacement and modernization products from your TRADELINE® wholesaler or distributor, refer to the
TRADELINE® Catalog or price sheets for complete ordering number.
If you have additional questions, need further information, or would like to comment on our products or services, please write or
phone:
1. Your local Home and Building Control Sales Office (check white pages of your phone directory).
2. Home and Building Control Customer Logistics
Honeywell Inc., 1885 Douglas Drive North
Minneapolis, Minnesota 55422-4386 (612) 951-1000
In Canada—Honeywell Limited/Honeywell Limitée, 155 Gordon Baker Road, North York, Ontario M2H 3N7.
International Sales and Service Offices in all principal cities of the world. Manufacturing in Australia, Canada, Finland, France,
Germany, Japan, Mexico, Netherlands, Spain, Taiwan, United Kingdom, U.S.A.
65-0237—1
Dimensions: See Fig. 1 and 2.
2-21/32 (68)
1-3/32 (28)
13/32
(11)
2-23/32 (69)
1-3/4 (45)
DIFFERENTIAL
CONNECTION
1/8 NPT
Fig. 1. C6097 1/4 in. NPT Mount dimensions in in. (mm).
2
27/32
(22)
1-17/32
HOLE
(90)
3-3/16
(81)
2-1/4
(57)
31/32
(25)
HOUSING
2-13/32
(61)
25/32
(21)
GAS CONNECTION
TERMINAL DIAGRAM
1/4 NPT WITH DUST SEAL
1
2
2-21/32 (68)
15/32 (12)
2-23/32 (69)
INDICATOR
3
NO
COM
NC
P
M17125

Hide quick links:

Advertisement

loading

This manual is also suitable for:

BC6097b