Flame Failure Response Time Setup - Honeywell 700 User Manual

Signal processor and viewing head
Hide thumbs Also See for 700:
Table of Contents

Advertisement

HONEYWELL MODEL 700/800 SIGNAL PROCESSOR AND VIEWING HEAD
SETTING FLAME FAILURE RESPONSE TIME
(FFRT)
FFRT
1/2/3 SEC
OPTION
2 SECS
INCREASE
DECREASE
66-2069—01
PRESS, FFRT,
FOR 2 SECONDS
Y
IS THE PANEL LOCKED?
N
USE INCREASE OR DECREASE KEYS
TO ADJUST SETTING
Fig. 23. Flow Chart 7: Flame Failure Response Time (FFRT) Setup.
DISPLAY SHOWS CURRENT
SETTING IN SECONDS
INCREASE
USE INCREASE OR DECREASE KEYS
TO ADJUST SETTING
DECREASE
DISPLAY SHOWS 'PL',
UNTIL KEY RELEASED
PRESS STORE TO SAVE
STORE
THE NEW SETTING
OR
PRESS RESET OR WAIT 4 SECONDS
RESET
TO RESTORE OLD SETTING
rE
NORMAL OPERATION