Register
Name
40001
FLAMECOUNT
40002
PROCSTATUS
40003
FLAMEON
40007
OUTPUTGAIN
40010
IRGAIN
40012
UVTGAIN
40017
TYPE
40021
TIMEDELAY
40022
FFRT
40023
VERSION
40024
MODEL
40084
ERRORCODE
40085
BAUD
40086
PARITY
40087
ADDRESS
40089
PROTOCOL
HONEYWELL MODEL 700/800 SIGNAL PROCESSOR AND VIEWING HEAD
Table 4. MODBUS registers map.
Description
Flame count of active viewing head (read only)
Processor status bitmask (read only)
bit 1:
flame on relay status (1=relay energized, 0=off)
bit 2:
Processor Lockout status (0 =lockout, 1=not lockout)
bit 3:
Panel access disabled (1=disabled, 0=enabled)
bit 4:
4 - 20 ma output (0=0 to 20, 1=4 to 20)
Flame On setpoint (read/write)
Gain of the 0/4-20mA output (read/write)
IR sensor gain setting (read/write)
UV tube gain setting (read/write)
Viewing head type bitmask (read only)
bit 0:
UV viewing head
bit 1:
IR viewing head
Time Delay (read only)
=1 for 700XXSP
Flame failure response time setting in seconds (read/write)
Firmware version (read only)
Model number (read only)
Error code (read/write)
NOTE: writing a non zero number to this register is not allowed
Baud rate setting (bits/second). Only affects RS-485
communication, not IRDA. (read, write)
96=9600 (default), 192=19200.
The SP and the master device must have the same baud
settings.
Parity setting. Only affects RS-485 communication, not IRDA.
(read/write)
0= none (default), 1=odd
Modbus address used by RS-485 and IRDA (read/write).
Each device must have a unique address.
Protocol (read/write)
0=Honeywell protocol, 1=Modbus protocol
17
Minimum
Maximum
0
3425
0
255
3 (S70X)
29
20
80
1
9
1
9
-
-
1
2
1
3
-
-
-
-
-
-
96
192
0
1
0
247
0
1
66-2069—01