Fire Display Lock

If several zones produce an alarm before any are silenced, the system can be
programmed to lock the keypad display with the first zone that produced an
alarm. Ask your installer if your system has been activated with this feature.
To display the other zone(s), press the [*] key for each zone. Also the "A",
"B", or "C" keys can be programmed to scroll the keypad display to view the
previous or subsequent fire alarms.

Fire Drill Test (Code + # + 69)

This test causes Notification Appliance Circuits to be activated (in either
steady or pulsing manner as programmed in the system), for the purpose of
conducting a fire drill or a bell test.
installer or a master user from Partition 1 keypads as follows:
1. Enter the corresponding security code and press [#} + 69 (make sure the
burglary portion of the system is disarmed). Keypads will display "FIRE
DRILL ACTIVE" while the test is active.
2. The test may be stopped by entering any security code and pressing OFF.
NOTE: The system continues to monitor all 24 hour zones (fire, panic, etc.),
while this test is active, and will end the test when an alarm condition is
detected. This test should be conducted at periodic intervals as determined
by the local authority having jurisdiction.
Fire Alarm System (cont'd)
This can only be activated by the
– 55 –