Download Print this page

Honeywell V4055A Product Data

On-off fluid power gas valve actuator
Hide thumbs Also See for V4055A:

Advertisement

V4055A,B,D,E
On-Off Fluid Power Gas
Valve Actuator

APPLICATION

The V4055 Gas Valve Actuator, in combination with a
a
VE5000
, V5055 or V5097 Gas Valve, controls the gas supply
to commercial and industrial burners.
When replacing a V4034 with a V4055, the V5034 gas valve
must also be replaced with a V5055 or V5097 gas valve.

FEATURES

• The V4055 Actuator, when used with the VE5000
V5097 or V5055 Valve, is rated for final safety shutoff
service.
• The V4055 Actuator can be used with the characterized
guide model of the V5055 or V5097 Gas Valve to
enhance lightoff smoothness.
• The standard model has an opening time of 26
seconds at 60 Hz or 32 seconds at 50 Hz. A fast-
opening model is available with timings of 13 seconds
at 60 Hz or 16 seconds at 50 Hz.
• Maximum closing time is one second, which meets
code, standard and insurer requirements.
• Models available with damper shaft, with or without
spring return; shaft extends out both sides and rides in
Teflon-like Delrin bushings; used with standard
7616BR Damper Crank Arm.
• Red OPEN indicator attached to actuator stem shows
when valve is even slightly open; yellow SHUT
indicator on valve stem shows only when gas valve is
fully closed.
• Models available with adjustable max flow limit switch.
• Ambient temperature rating is -40°F to +150°F (-40°C to
+66°C) for 60 Hz models and -10°F to +158°F (-23°C to
+70°C) for 50 Hz and 50/60 Hz models.
• Valve and actuator combinations can be mounted in
any position, with the exception of the 220 to 240 Vac,
50/60 Hz models, which are mounted vertically.
• Models available with factory-installed single pole
double throw (spdt) field-adjustable Auxiliary Switch.
Field-addable Auxiliary Switch kits are also available.
• Standard enclosure meets NEMA 1 (IP30)
requirements; models available with NEMA 4 (IP54)
weatherproof enclosure.
• V4055D and high pressure V4055E with Proof-of-
Closure Switch and V5055/V5097C or E with valve seal
overtravel interlock (double seal) to meet specific
a
,
code, standard and insurer requirements.
a
VE5000 is a European manufactured and approved valve for
European use only.
Application ........................................................................
Features ...........................................................................
Specifications ...................................................................
Ordering Information ........................................................
Installation ........................................................................
Wiring ...............................................................................
Checkout and Service ......................................................
PRODUCT DATA
Contents
1
1
2
2
4
6
7
60-2309-13

Advertisement

loading

Summary of Contents for Honeywell V4055A

  • Page 1: Table Of Contents

    V4055A,B,D,E On-Off Fluid Power Gas Valve Actuator PRODUCT DATA • The V4055 Actuator can be used with the characterized guide model of the V5055 or V5097 Gas Valve to enhance lightoff smoothness. • The standard model has an opening time of 26 seconds at 60 Hz or 32 seconds at 50 Hz.
  • Page 2: Specifications

    If you have additional questions, need further information, or would like to comment on our products or services, please write or phone: 1. Your local Honeywell Automation and Control Products Sales Office (check white pages of your phone directory). 2. Honeywell Customer Care...
  • Page 3 V4055A,B,D,E ON-OFF FLUID POWER GAS VALVE ACTUATOR Table 3. V4055A,D Electrical Ratings. Opening (Standard) Opening (Fast) Holding Voltage and Frequency Inrush Inrush (VA) (VA) — 43.0 0.91 — 58.0 1.30 10.4 0.16 100/50-60 — 33.0 — 43.0 0.91 0.14 100/50-60 120/60 50.0...
  • Page 4: Installation

    V4055A,B,D,E ON-OFF FLUID POWER GAS VALVE ACTUATOR Accessories: 7616BR Damper Crank Arm (damper arm and clip). 133568 Auxiliary Switch Bag Assembly (not for models with maximum flow limit switch). Available Models: V4055 with NEMA 4 enclosure 133569 Valve-Closed Indication Switch Bag Assembly.
  • Page 5 V4055A,B,D,E ON-OFF FLUID POWER GAS VALVE ACTUATOR Mount Actuator on Valve IMPORTANT 1. All wiring must comply with all applicable electrical 1. Check the final position of the valve body to be sure that codes, ordinances, and regulations. All wiring must the actuator is in the proper position when mounted on be NEC Class 1.
  • Page 6: Wiring

    V4055A,B,D,E ON-OFF FLUID POWER GAS VALVE ACTUATOR stroke. 7616BR DAMPER 52 DEGREE ANGULAR ROTATION 2-5/16 (58.7) SHAFT MAXIMUM TRAVEL PROOF-OF-CLOSURE SWITCH AUXILIARY SWITCH 2-11/16 (68.3) RADIUS M7322 Fig. 3. 7616BR Damper Crank Arm can be attached to actuator shaft to drive a damper when valve is open.
  • Page 7: Checkout And Service

    V4055A,B,D,E ON-OFF FLUID POWER GAS VALVE ACTUATOR CHECKOUT AND SERVICE 7. If the valve bonnet assembly is in good condition and is not replaced, replace the bonnet seal. Do not reuse the old bonnet seal. See Table 9 below for the seal number.
  • Page 8 V4055A,B,D,E ON-OFF FLUID POWER GAS VALVE ACTUATOR Each replacement assembly contains the bonnet assembly, two rubber seals, and a tube of grease. It must be used only on the type of valve indicated above. Table 9. Gas Valve Replacement Seals.

This manual is also suitable for:

V4055bV4055dV4055e