The V9055 Gas Valve Actuator in combination
with the V5055 Gas Valve provides modulating
control of the gas supply to commercial and indus-
trial burners.
Actuator opens the valve to the low-fire position
when energized. Actuator then modulates to meet
firing rate controller (Series 90) demand.
Actuator is equipped with an integral shaft that may
be used to drive a combustion air damper in unison
with the gas valve.
The V5055 Gas Valve includes a yellow SHUT
indicator. The actuator includes a red OPEN indica-
tor. The indicators provide constant visual indication
of valve position.
Actuator can be used with all V5055 Valve models;
however, the V5055B with characterized guide is
recommended for optimum control and low-fire
repeatability.
Ambient temperature range for 60 Hz models is -40° F
to 125° F [-40° C to 53° C]. Ambient temperature
range for 50 Hz and 50/60 Hz models is -10° F to
125° F [-23° C to 52° C].
Auxiliary 1/2 hp rated switch is available for field
installation.
Integral damper shaft provides a maximum of 20 lb
[9 kg] of force.
Modulating Fluid Power
Gas Valve Actuator
F.P. • Rev. 9-94 • ©Honeywell Inc. 1994 • Form Number 60-2311-6
1
V9055A,D
Valve and actuator may be mounted in any position.
Model is available with NEMA 4 (weatherproof)
enclosure.
V9055D/V5055C,E combinations available with
proof-of-closure switch and two valve seals (valve
seal overtravel interlock) to meet specific code/stan-
dard/insurer requirements.
Field addable adapter available for 4-20 dc mA con-
trol of actuator.
When replacing a V9034 Actuator with a V9055, the
V5034 Valve body must also be replaced with a
V5055 Gas Valve.
CONTENTS
Installation ..................................................... 4
Wiring ............................................................. 5
Adjustments .................................................... 6
Operation ....................................................... 7
60-2311-6