Wiring Schematics - Honeywell ML7984B User Manual

Valve actuator

Advertisement

4
SIGNAL
SOURCE
+
2-10 Vdc
PWM
Allow 0.5 amps maximum for each device. Actuators and controller can share same transformer providing the
1
VA rating of the transformer is not exceeded and proper phasing is observed.
2
"T5" and "W" terminals are factory connected internally. Device is compatible with the 3-wire control system.
Use configuration DIP switches to select device functions: Direct acting function ( actuator stem moves upwards
3
with signal increases ) or Reverse acting function ( actuator stem moves downwards with signal increases ).
4
Use either one controller only
PWM: min. 0.1 sec + 0.01 sec increments (max. 2.65 sec )
PWM: min. 0.1 sec + 0.02 sec increments (max. 5.20 sec )
PWM: min. 0.1 sec + 0.05 sec increments (max. 12.85 sec )
PWM: min. 0.1 sec + 0.10 sec increments (max. 25.6 sec )
PWM: min. 0.59 sec + 0.00918 sec increments (max. 2.93 sec ) NOVAR
Analog: 2-10 Vdc
Configuration DIP switches
located adjacent to the input
terminal block
3
ML7984B
R
T6
W
B
T5
C
MODE
Fig. 7 Wiring for ML7984B actuators
2
24 Vac
on
off
on
off
on
off
on
off
on
off
on
off
NOTE:
Turn power off before setting the DIP switches.
5
1
OR
+
T6
28 Vdc
-
T5
DIP SWITCH
1
2
3
on
off
1
3
2
Direct
Acting
1
3
2
on
1
2
3
off
Reverse
1
3
2
Acting
1
2
3
ML7984B
WIRING
L1
L2
4
4