Removing A Hot-Swappable Chassis Fan Unit - HP Integrity rx4640 Service Manual

Hide thumbs Also See for Integrity rx4640:
Table of Contents

Advertisement

are in the left and center positions. Fan unit 2 is smaller and only fits into the right-most position
(behind the power supply).
CAUTION:
follow ESD safety precautions can result in damage to the server.
When the server is running, the top cover must be replaced within two minutes to prevent
components from overheating. If the top metal cover is not replaced within five minutes, the
server automatically shuts down.
NOTE:
A hot-swappable device does not require interaction with the operating system before
the device is removed from or installed into the server.
The AC power to the server does not have to be off to remove or replace a hot-swappable chassis
fan.

Removing a Hot-Swappable Chassis Fan Unit

To remove a hot-swappable chassis fan unit, follow these steps:
1.
If rack mounted, slide the server out from the rack until it stops. See
From the Rack" (page
2.
Remove the top cover. See
Observe all ESD safety precautions before attempting this procedure. Failure to
31).
"Removing the Top Cover" (page
36).
Removing and Replacing Hot-Swappable Chassis Fans
"Extending the Server
53