Disable All Control, Extinguishing, Ventilation And Alarm Device Outputs (H2/B4) - Panasonic MEW01091 Operating Instructions Manual

Fire alarm system
Table of Contents

Advertisement

Panasonic Electric Works Nordic AB
MEW01091
25.4
Action
"Access"
Scroll to menu H2.
"A"
Scroll to menu B4.
"A"
Press 0, 1, 2 or 3
"A"
"Return"
Rev: 3
Disable all control, extinguishing, venti-
lation and alarm device outputs (H2/B4)
Outputs programmed as type Control (general), type Fire ventilation,
type Extinguishing system and type Alarm devices can for the type
respectively be disabled all at the same time. Disabled output means
that even if the control expression (trigger condition) for the output
respectively is fulfilled (true), the output will not be activated.
Disabled outputs are shown in menu H4/U1.
The outputs will be disabled until re-enabled again (via H2/B8).
NOTE! This function for alarm devices is not the same as for push
button "Silence alarm devices" (P3), see chapter "Silence Alarm
devices", page 27. This function has higher priority than "Silence
alarm devices".
Text in display
Disable or re-enable
Disable zone
Disable all control,
or alarm device outputs
Disable type:
0 0=Control 1=Ventilation
2=Exting 3=Alarm devices
Disable all control,
or alarm device outputs
Disable or re-enable
EBL128 Operating Instructions V1.1.x
ACCEPT? H2
ACCEPT? B1
ventilation, exting
ACCEPT? B4
ACCEPT?
ventilation, exting
ACCEPT? B4
ACCEPT? H2
85
Comments
According to chapter
"Access", see page 78.
Press:
"0"=control output
"1"=
ventilation
output
"2"=
extinguishing
output
"3"=alarm device output.
Press "A" to accept.
LED "Disablements" (L8)
will light up.
If type 3 = alarm devices
are disabled also the LED
"Fault / Disablements
Alarm devices" (L13) will
light up.
Scroll or press "Return" to
menu H2. Scroll or press
"Return" to log off.