T7351 COMMERCIAL PROGRAMMABLE THERMOSTAT
Text
Default
TMP LIM
3
0 - 5
TMP OCC 3
1 - 8
TMP CAL
0
-4 - 3
MINCOOL 45° F
45° - 99° F
(7° C)
(7° - 37° C)
MAXHEAT 90° F
40° - 90° F
(32° C)
(4° - 32°)
HEATLCK
NO
YES or NO
HTLCKSP 70° F
-40° - 120 ° F
(21° C)
(-40° - 49° F)
COOLLCK NO
YES or NO
CLLCKSP
35° F
-40° - 120° F
(2° C)
(-40° - 49° C)
DAT LL
NO
YES or NO
DATLLSP
45° F
35° - 60° F
(7° C)
(2° - 16° C)
DAT HL
NO
YES or NO
DATHLSP
110° F
65° - 140° F
(43° C)
(18° - 60° C)
DEHUMID 0
0 - 5
DEH MIN
5
5 - 15
DEH TMP
2
1 - 5
MINHTRT
5
0 - 20 DDF/HR Minimum Heat Recovery Ramp Rate
MAXHTRT 8
0 - 20 DDF/HR Maximum Heat Recovery Ramp Rate (Only Displayed if Outdoor Sensor is
MINHTOA 0° F
-20° - 120° F
(-18°
(-29° - 49° C)
C)
MAXHTOA 40° F
-20° - 120° F
(4° C)
(-29° - 49° C)
MINCLRT
3
0 - 20 DDF/HR Minimum Cool Recovery Ramp Rate
MAXCLRT 6
0 - 20 DDF/HR Maximum Cool Recovery Ramp Rate (Only Displayed if Outdoor Sensor is
MINCLOA
90° F
-20° - 120° F
(32° C)
(-29° - 49° C)
MAXCLOA 70° F
-20° - 120° F
(21° C)
(-29° - 49° C)
62-0258—05
Table 3. Installer Setup. (Continued)
Choices
Temporary Setpoint Adjustment
0: 0 Deg. F
1: 1 Deg. F
2: 2 Deg. F
3: 3 Deg. F
4: 4 Deg. F
5: 5 Deg. F
Temporary Occupied Duration
1 to 8 hours
Temporary Display Adjustment
0 - 3 = 0 to 3 DDF
4 - 7 = -4 to -1 DDF
Min Cool Setpoint
Max Heat Setpoint
Heating Lockout (Only displayed if Outdoor Air Sensor is selected)
NO: None
YES: Enabled
Heating Lockout Temperature
(Display only if Remote Outdoor Air Sensor is configured)
Cooling Lockout (Only displayed if Outdoor Air Sensor is Selected)
NO: None
YES: Enabled
Cooling Lockout Temperature
(Display only if Remote Outdoor Air Sensor is configured)
Discharge Low Limit (Only displayed if Discharge Air Sensor is Selected)
NO: None
YES: Enabled
Discharge Low Temp Limit
(Display only if Discharge Sensor is configured)
Discharge High Limit (Only displayed if Discharge Air Sensor is Selected)
NO: None
YES: Enabled
Discharge High Temperature Limit
(Display only if Discharge Sensor is configured)
Dehumidification
0: None
1: MinOn Time
2: Reset Temp Setpoint
3: Reset w/ MinOn
4: Reheat
5: Reheat w/ Min On
Dehumidify Minutes On
Dehumidify Temp Reset
Selected)
Minimum Heat Outdoor Air Temperature (Only Displayed if Outdoor Sensor is
Selected)
Maximum Heat Outdoor Air Temperature (Only Displayed if Outdoor Sensor is
Selected)
Selected)
Minimum Cool Outdoor Air Temperature (Only Displayed if Outdoor Sensor is
Selected)
Maximum Cool Outdoor Air Temperature (Only Displayed if Outdoor Sensor is
Selected)
Notes
6