T7351 COMMERCIAL PROGRAMMABLE THERMOSTAT
Dehumid Hot Gas BP
The auxiliary output operates as shown in Table 6.
Table 6. Hot Gas Bypass Dehumidification Logic.
Humidity
Cooling Stages Active Auxiliary Output
High
more than one
High
one or less
Low
more than one
Low
one or less
62-0258—05
Auxiliary output during call for multiple cooling stages for
two reasons:
De-energized
Energized
De-energized
De-energized
10
1. This method assumes that the cooling provides
dehumidification.
2. Multiple cooling stages probably provide necessary
dehumidification.
3. Hysteresis and a minimum timer prevent short
cycling of this output.