Honeywell T7351F2010 - Digital Thermostat, 3h Installation Instructions Manual page 5

Commercial programmable thermostat for single- or multi-stage conventional/heat pump systems
Table of Contents

Advertisement

Text
Default
HEATPMP 0
0 - 2
COOLSTG 1
0 - 4
HEATSTG 1
0 - 3
AUX STG
0
0 - 2
AUX CON
0
0 - 3
WALLMOD 0
0 - 3
OATSENS 0
0 - 1
DATSENS 0
0 - 1
HUMSENS 0
0 - 2
OCCSENS 0
0 - 1
FAN HT
0
0 - 1
XFAN HT
YES
YES or NO
XFAN CL
NO
YES or NO
STRTDEL
0
0 - 15
ADVANCE NO
YES or NO
Table 3. Installer Setup. (Continued)
Choices
Application Type Selection
0: Conventional
1: Heat Pump - Cooling (Energize O/B on call for cool)
2: Heat Pump - Heating (Energize O/B on call for heat)
Number of Cooling Stages
0: 0 Stages of Cooling
1: 1 Stages of Cooling
2: 2 Stages of Cooling
3: 3 Stages of Cooling (Not available if Heat Pump is selected)
4: 4 Stages of Cooling (W3 will be used as 4th stage relay) (Not available if Heat
Pump is selected)
Number of Heating Stages (Not available if Heat Pump is selected)
0: 0 Stages of Heating
1: 1 Stages of Heating
2: 2 Stages of Heating (This is the max if 4 cooling stages is selected)
3: 3 Stages of Heating
Number of Heat Pump Heating Stages (Only shown when Heat Pump is
selected)
0: 0 Aux Stages
1: 1 Aux Stages
2: 2 Aux Stages
Aux Contact Functionality
0: Time of Day
1: Economizer
2: Dehumid - Hot Gas Bypass
3: Simple Dehumid
Remote Room Sensor Selection
0: Local sensor only
1: TR21/TR24 and T7770A/D (Remote Sensor, No Remote Setpoint, Bypass 0)
2: TR22/TR23 and T7770B/C (Remote Sensor, Remote Setpoint, Bypass 0)
3: T7771 (Remote sensor, Remote Setpoint, Bypass 1)
(Bypass 0 means that by pressing the override button the thermostat goes from
unoccupied to occupied and the LED will light up and the temporary occupied
timer will begin. If the button is pressed again, the timer will restart.)
(Bypass 1 means that by pressing the override button a second time the
thermostat can return to the unoccupied period.)
Outdoor Air Sensor Selection
0: None
1: Remote Outdoor Air Sensor
Discharge Air Sensor Selection
0: None
1: Remote Discharge Air Sensor
Room Humidity Sensor selection
0: None
1: On Board Sensor
2: Remote Sensor
Occupancy Sensor Selection
0: None
1: Remote Occ Sensor
Fan Operation on Heat
0: Conventional (Equipment controls Fan)
1: Electric (Thermostat turns on Fan with call for Heat)
Extended Fan on Heat
NO: None
YES: 90 seconds
Extended Fan on Cool
NO: None
YES: 40 seconds
Sequential Start Delay
0 to 150 seconds in 10 second increments
Advanced Settings
NO: Hide
YES: Show
T7351 COMMERCIAL PROGRAMMABLE THERMOSTAT
Notes
5
62-0258—05