CfgAlarmTVOCLimitEnable
cfgDisplayUnitTVOC
4.4.5.7 Configuration Points
SS_MV_AQI_level
cfgAQIUnhealthyScore
cfgAQIModerateScore
CfgAlarmAQIDeadband
CfgAlarmAQITimeDelay
CfgAlarmAQILimitEnable
TR50 - User Guide
Point Name
BACnet
Point Name
Instance
6
251
252
253
254
26
BACnet
Read/
Type
Instance
Write
25
R/W
Multi State
Value
102
R/W
Multi State
Value
Read/
Type
Write
R
Multi State Value
R/W
Analog Value
R/W
Analog Value
R/W
Analog Value
R/W
Analog Value
R/W
Multi State Value
Default
Range
Value
4
1:TVOC High Limit
And High High
Limit Disable
2:TVOC High Limit
Enable
3:TVOC High High
Limit Enable
4:TVOC High Limit
And High High
Limit Enable
1
1: Parts Per Billion
2: Micrograms Per
Cubic Meter
Default
Range
Value
1
1: Good
2: Moderate
3: Unhealthy
40
0
<= PRESENT VALUE of
cfgAQIUnhealthyScore
<= PRESENT VALUE of
cfgAQIModerateScore
80
PRESENT VALUE of
cfgAQIUnhealthyScore
<= PRESENT VALUE of
cfgAQIModerateScore
<=100
2
0 <= PRESENT VALUE of
cfgAlarmAQIDeadband
60(s)
0 <= PRESENT VALUE of
cfgAlarmAQITimeDelay
4
1: AQI Moderate Limit
And Unhealthy Limit
Disable
2: AQI Moderate Limit
Enable
3: AQI Unhealthy Limit
Enable
4: AQI Moderate And
Unhealthy Limit Enable
23