Honeywell TR50 User Manual page 23

Indoor air quality sensor
Hide thumbs Also See for TR50:
Table of Contents

Advertisement

4.4.5.1 Input Points
SS_AI_SensorReading_Temp
SS_AI_SensorReading_Humi
SS_AI_SensorReading_CO
SS_AI_SensorReading_PM2.5
SS_AI_SensorReading_TVOC
SS_AI_AIR_QUALITY_SCORE
SS_AI_SensorReading_PM1.0
SS_AI_SensorReading_PM10
4.4.5.2 Temperature Configuration Points
CfgAlarmTempLowLimit
CfgAlarmTempHighLimit
CfgAlarmTempDeadband
CfgAlarmTempTimeDelay
18
Out of Range reading
Alarm set values
LCD Brightness
Point Name
2
Point Name
BACnet
Read/
Instance
Write
1
Read
2
Read
3
Read
4
Read
5
Read
6
Read
7
Read
8
Read
BACnet
Read/
Type
Instance
Write
1
R/W
Analog
Value
2
R/W
Analog
Value
3
R/W
Analog
Value
4
R/W
Analog
Value
Type
Range
Analog Input
32-122 (
o
0-50 (
C)
Analog Input
0-100 (%)
Analog Input
0-9999 (ppm)
Analog Input
0-5000 (ug/m
Analog Input
8-2820 (ppb)
16-5640 (ug/m
Analog Input
0-100
Analog Input
0-5000 (ug/m
Analog Input
0-5000 (ug/m
Default
Value
o
o
65(
F)
32
F <= PRESENT VALUE of
cfgAlarmTempLowLimit <=
o
18(
C)
PRESENT VALUE of
cfgAlarmTempHighLimit
o
0
C <= PRESENT VALUE of
cfgAlarmTempLowLimit <=
PRESENT VALUE of
cfgAlarmTempHighLimit
PRESENT VALUE of
o
86(
F)
cfgAlarmTempLowLimit
o
30(
C)
<= PRESENT VALUE of
cfgAlarmTempHig Limit<=
o
122
F
PRESENT VALUE of
cfgAlarmTempLowLimit <=
PRESENT VALUE of
cfgAlarmTempHighLimit<=
o
50
C
o
o
1(
F)
0(
F) <= PRESENT_VALUE of
o
cfgAlarmTempDeadband
1(
C)
o
0(
C) <= PRESENT_VALUE of
cfgAlarmTempDeadband
60(s)
0(s) <= PRESENT_VALUE of
cfgAlarmTempTimeDelay
TR50 - User Guide