WORKING RANGE
4 WORKING RANGE
4.1 POWER SUPPLY WORKING RANGE
Nominal power supply
•
Single phase: 1~ 230V 50Hz
•
Three phase: 3N~ 400V 50Hz
Operating voltage
Between 90 and 110% of the nominal voltage.
Voltage imbalance for nominal power supply 3N~ 400V 50Hz
Up to 3% of each phase, measured at the main terminal of the outdoor unit.
Starting voltage
Always higher than 85% of the nominal voltage.
4.2 R410A TEMPERATURE WORKING RANGE
MODEL
Water temperature
Indoor ambient temperature
4.2.1 Space heating
YUTAKI (S / S COMBI)
Water outlet
temperature (Cº)
Continuous working range.
Outdoor unit operation is possible, but the capacity is not guaranteed. Indoor unit and back-up heater are operating.
Only back-up heater. (No outdoor unit operation).
20
PMML0510 rev.1 - 10/2019
2.0HP
ºC
(2.0-3.0)HP
Ambient temperature
(ºC (DB))
2.5HP
3.0HP
4.0HP
Refer to the graphics for each case
5~30
Water outlet
temperature (Cº)
5.0HP
6.0HP
8.0HP
(4.0-10.0)HP
Ambient temperature
(ºC (DB))
10.0HP