How to put a detection Zone in test
01
Select the Menu icon
02
Select the 'Test Type' tab
03
Check the required Zone
04
Select the 'Proceed' button
The Outputs are not activated when a Zone is placed in Test Mode.
05
Select the 'Start Test'
'Voice Alarm' and 'Fire Brigade' will be made inactivate during Test.
06
On completion of a Zone tests you can select the 'Zone in Test' button and then select the 'End Test' button
to end Zone Test or move on to another Zone to test by selecting 'Edit Test' and then checking the required
next Zone to test.
How to test the panels LEDs and Display
01
Select the Menu icon
02
Select 'Test Type' tab
03
Select the 'START INDICATOR TEST'
sounds and momentarily the screen colour will rotate between Green, Red and Blue.
04
To stop the test you must touch the screen and select the 'STOP INDICATOR TEST' button
INSPIRE E10/E15 Control Panels - Operating instructions
and then select 'Test System'
and then select 'Test Mode - Detection Test'
to put into Test. Note you can select multiple Zones.
.
button and note the 'Test' LED is lit and note the Outputs like 'Alarm Devices',
and then select the 'Test System'
.
button and observe all the LEDs on the panel are lit, the buzzer
.
.
button.
.