Receptacles/Sub-Bases

Tandem
Perpendicular
230/208V 15 Amp
230/208V 20 Amp
NEMA6-15R
NEMA6-20R
Sub-Bases
RAK204U
Voltage
N/A
Amps
N/A
Receptacle
N/A
230/208 Volt sub-bases include appropriate power cord kit.
265 Volt units are to be direct connected. Cordset through enclosed chaseway into interior sub-base receptacle meets the NEC requirements.
* Not approved for use on 7000 BTU models.
Power connection kits are required on all Zoneline
The correct kit for the installation is determined by the voltage and amperage of the electrical circuit and the means of connecting the unit to the
building wiring. If the unit is to be plugged into a receptacle, a line cord kit would be used; if the unit is to be permanently connected, a permanent
connection kit would be used. 265 volt cord set units must be installed in compliance with National Electrical Code
Power connection kits
Required on all models.
See specification sheet
for heater KW and branch
circuit ampacity.
RAK3153A/3203A
230/208 volt line cord
connection kit
230/208 Volt Line Cord Connected Units
LCDI Power Connection Kit
RAK3153A
Heater KW
Watts
2400/2320
BTUH
8100/7900
Amps
Min. circuit amps
Recommended
protective
time delay
device
fuse or breaker
230/208 Volt Direct Connection Kit**
Heater KW
Watts
2400/2320
BTUH
8100/7900
Amps
Min. circuit amps
Recommended
protective
time delay
device
fuse or breaker
* Not approved for use on 7000 BTU models.
** To be used with sub-base or connection to building wiring
Large tandem
230/208V 30 Amp
*
NEMA6-30R
RAK204D15P
RAK204D20P
230/208
230/208
15
20
NEMA6-15R
NEMA6-20R
RAK4157/4207/4307
230/208 volt universal
power supply kit
RAK3203A
2.40/2.32
3.30/3.20
3300/3200
11200/10900
11.0/11.6
15.1/16.0
15
20
15 Amp
20 Amp
time delay
fuse or breaker
fuse or breaker
RAK4157
RAK4207
2.40/2.32
3.30/3.20
3300/3200
11200/10900
11.0/11.6
15.1/16.0
15
20
15 Amp
20 Amp
time delay
fuse or breaker
fuse or breaker
265V 15 Amp
NEMA7-15R
RAK204D30P*
RAK204E15
230/208
30
NEMA6-30R
NEMA7-15R
®
chassis (see chart below).
RAK5157/5207/5307
265 volt universal power
supply kit
265 Volt Permanent Connected Units**(Cord set)
RAK3303A*
RAK5172
4.70/4.53
2.40
4700/4530
2400
16000/15400
8100
21.2/22.4
9.9
30
15
30 Amp
15 Amp
time delay
time delay
fuse
* Not approved for use on 7000 BTU models.
** To be used with sub-base
265 Volt Direct Connection Kit**
RAK4307*
RAK5157
4.70/4.53
2.40
4700/4530
2400
16000/15400
8100
21.2/22.4
9.9
30
15
30 Amp
15 Amp
time delay
time delay
fuse
* Not approved for use on 7000 BTU models.
** To be used with sub-base or connection to building wiring
– 18 –
265V 20 Amp
265V 30 Amp
NEMA7-20R;
NEMA7-30R;
receptacle used
receptacle used
On 265V sub-base
On 265V sub-base
GE0720-3
GE073
RAK204E20
265
265
15
20
NEMA7-20R
NEMA7-30R
®
.
RAK5202
RAK5302*
3.40
4.80
3400
4800
11600
16300
13.3
18.6
20
30
20 Amp
30 Amp
time delay
time delay
fuse
fuse
RAK5207
RAK5307*
3.40
4.80
3400
4800
11600
16300
13.3
18.6
20
30
20 Amp
30 Amp
time delay
time delay
fuse
fuse
RAK204E30
265
30