7800 SERIES S7800A1142 KEYBOARD DISPLAY MODULE
Table 21. 7800 SERIES Sequence State Codes
and Associated register code values.
7800 SERIES
Register
Sequence
40003
State
Fault
LOCKOUT
code not
zero
0
UNUSED HISTORY 0
1
INITIATE
2
INITIATE HOLD: AC
FREQUENCY/
NOISE
3
INITIATE HOLD:
AC LINE DROPOUT
4
INITIATE HOLD:
AC FREQUENCY
5
INITIATE HOLD:
LOW LINE
VOLTAGE
6
STANDBY
7
STANDBY HOLD:
REM
REMOTE CONTROL
8
STANDBY HOLD:
START SWITCH
9
STANDBY HOLD: F/G
FLAME DETECTED
10
STANDBY HOLD:
T20
PRE-IGNITION
11
STANDBY HOLD: T7
RUNNING
INTERLOCK
12
STANDBY HOLD: T7
LOCKOUT
INTERLOCK
13
STANDBY HOLD:
AIRFLOW SWITCH
14
PURGE HOLD: T19
HIGH FIRE
SWITCH
15
PURGE DELAY:T19
HIGH FIRE
JUMPRD
16
PURGE HOLD:
TEST
RUN/TEST SWITCH
17
PURGE DELAY: T18
LOW FIRE JUMPRD
18
PURGE HOLD: F/G
FLAME DETECTED
19
PURGE
20
PURGE HOLD: T18
LOW FIRE SWITCH
21
PuRGE HOLD: T7
Running Interlock
65-0288-1
String Code
Burner
Control
Line
Line
Uses
State
1
2
mm:ss
Bits
52
Table
8000h
24
0
0000h
48
0
3
0001h
49
8
4001h
49
9
4001h
49
7
4001h
49
60
4001h
103
0
0002h
104
94
4002h
104
106
4002h
104
35
4002h
104
86
4002h
104
101
4002h
104
54
4002h
104
13
4002h
93
40
4004h
89
39
4004h
93
98
4004h
89
56
4004h
93
35
4004h
87
0
3
0004h
93
58
4004h
93
101
4004h
Table 21. 7800 SERIES Sequence State Codes
and Associated register code values. (Continued)
7800 SERIES
Register
Sequence
40003
State
22
PURGE HOLD:
LOCKOUT
INTERLOCK
23
PURGE HOLD:
AIRFLOW SWITCH
24
PURGE HOLD:
START SWITCH
25
PILOT IGN
26
PILOT HOLD: TEST
RUN/TEST
SWITCH
27
PILOT HOLD:
START SWITCH
28
MAIN IGN
29
MAIN IG HOLD:
MANUAL-OPEN
SWITCH
30
RUN
31
RUN PV HOLD:
LOW FIRE SWITCH
32
PVHOLD IGN
33
PV HOLD:
PV HOLD SWITCH
34
RUN/LOWFIRE:
TEST
RUN/TEST
SWITCH
35
POSTPURGE
36
STATE UNKNOWN 31
37
RESET/ALARM
TEST
38
SAFETY START
39
SAFETY1-1
40
SAFETY1-2
41
SAFETY1-3
42
SAFETY1-4
43
SAFETY1-5
44
Blank
45
PRE-IGNITION
46
SAFETY 1
47
PILOT STAB.
48
MAIN TRIAL
49
MAIN TRIAL
50
STANDBY HOLD:
RUN/TEST
SWITCH
51
STATE 51
52
STATE 52
53
SAFETY
RUN/TEST
SWITCH
42
String Code
Burner
Control
Line
Line
Uses
State
1
2
mm:ss
Bits
93
54
4004h
93
13
4004h
93
106
4004h
78
0
0008h
3
77
98
4008h
77
106
4008h
66
0
0010h
3
67
72
4010h
95
0
0020h
96
58
4020h
77
46
3
4008h
77
45
4008h
97
98
4020h
83
0
3
0040h
0
6000h
111
0
6000h
102
105
4002h
102
2
3
0008h
102
3
3
0008h
102
4
0008h
3
102
5
3
0008h
102
6
3
0008h
0
0
A000h
84
0
0080h
3
102
1
3
0008h
79
0
0008h
68
0
3
0010h
68
0
0010h
104
98
4002h
31
0
A000h
31
0
A000h
102
98
4008h