Process Pid Set 1 - ABB ACS880-x04 Firmware Manual

Primary control program
Table of Contents

Advertisement

No.
Name/Value
37.41
ULC overload timer
0.0 ... 10000.0 s
37.42
ULC underload
timer
0.0 ... 10000.0 s
40

40 Process PID set 1

40.01
Process PID output
actual
-32768.00 ...
32767.00
40.02
Process PID
feedback actual
-32768.00 ...
32767.00
40.03
Process PID
setpoint actual
-32768.00 ...
32767.00
40.04
Process PID
deviation actual
-32768.00 ...
32767.00
Description
Defines the time for which the monitored signal must
continuously stay above the overload curve before the drive
takes the action selected by
Overload timer.
Defines the time for which the monitored signal must
continuously stay below the underload curve before the drive
takes the action selected by
Underload timer.
Parameter values for process PID control.
The drive contains a single active PID controller for process
use, however two separate complete set-ups can be
programmed and stored.
The first set is made up of parameters 40.07...40.56*, the
second set is defined by the parameters in group
PID set
2. The binary source that defines which set is used is
selected by parameter
40.57 PID set1/set2
See section
Process PID control
chain diagrams on pages
*The remaining parameters in this group are common for both
sets.
Displays the output of the process PID controller. See the
control chain diagram on page 599.
This parameter is read-only. The unit is selected by parameter
40.12 Set 1 unit
selection.
Process PID controller output.
Displays the value of process feedback after source selection,
mathematical function (parameter
function), and filtering. See the control chain diagram on page
598.
This parameter is read-only. The unit is selected by parameter
40.12 Set 1 unit
selection.
Process feedback.
Displays the value of process PID setpoint after source
selection, mathematical function
function), limitation and ramping. See the control chain
diagram on page 599.
This parameter is read-only. The unit is selected by parameter
40.12 Set 1 unit
selection.
Setpoint for process PID controller.
Displays the process PID deviation. By default, this value
equals setpoint - feedback, but deviation can be inverted by
parameter
40.31 Set 1 deviation
chain diagram on page 599.
This parameter is read-only. The unit is selected by parameter
40.12 Set 1 unit
selection.
PID deviation.
37.03 ULC overload
actions.
37.04 ULC underload
selection.
(page 66), and the control
598
and 599.
40.10 Set 1 feedback
(40.18 Set 1 setpoint
inversion. See the control
Parameters 311
Def/FbEq16
20.0 s
1 = 1 s
20.0 s
actions.
1 = 1 s
41 Process
-
1 = 1 unit
-
1 = 1 unit
-
1 = 1 unit
-
1 = 1 unit