NFC functionality and parameter settings
Parameters can be set via the supporting app using the NPC function. The maximum flow rate can be set on the parameter settings
interface. On the settings interface, select the "Advanced Settings" option to configure the maximum opening, dead zones and
sensitivity. After configuring the settings, move your device close to the actuator to upload the set parameters. A prompt will
be displayed in the app indicating that the settings have been uploaded. Return to the parameter settings interface and move
your device close to the actuator to view the configured parameters.
Note: As you need to configure a maximum flow rate for the PICV, we do not recommend configuring a maximum opening. If you have
configured a maximum opening, this will override the maximum flow rate.
Parameter
Language
Chinese, English, Auto
Valve mode
VPIC series PICV, DN25–DN150
Maximum flow rate
30%–100% of the PICV's maximum flow rate
Dead zone
1.0–10.0
Sensitivity
0.5–10.0
Maximum opening
30%–100%
NOTE:
1. To ensure the physical security of the device, it can only be accessed by authorized personnel.
2. Ensure the secure installation, deployment and operation and maintenance management of the device.
3. Models with NFC configuration functionality must be used in conjunction with the dedicated app provided by Honeywell.
4. Install the app on a dedicated phone, ensuring that it has not been jailbroken or that the firmware has not been replaced.
Regularly scan the phone for viruses and check the app permissions.
5. If a fault occurs during use of the app, please report the error code to Honeywell.
6. If you find a vulnerability in the security system, please contact https://www.honeywell.com/en-us/product-security
Set range or options
6
FD-BV-06.2019-V01