SPECIFICATIONS SUMMARY

GENERAL
Thermocouple Accuracy
Type J, Type K, Type E:, Type T:
Type R & S:
Thermocouple Range
Type J:
Type K:
Type E:
Type T:
Type R & S:
Thermocouple Warm up Period: 45 minutes
Thermocouple Zero Drift:
Open Thermocouple Detection: Up scale
Thermocouple Lead Resistance: 100 ohms max.
RTD:
curve
RTD Accuracy:
RTD Range:
Open RTD Detection:
Process (Voltage or current)
Input Accuracy:
Voltage Input Range:
Current Input Range:
Sampling Rate:
General Power:
Operating Conditions:
condensing
Protection:
Dimensions:
Panel Cutout:
Weight:
800
R/T
300
SPEED:1s
ELAPS:00:01:08
PRESS
PRESS
800
LOG
F:1
300
SPEED:1s
ELAPS:00:01:08
PRESS
800
LOG
F:1
300
PRESS
01/03/2012
03:54:35 PM
SCROLL FORWARD THROUGH DATA.
MOVE FORWARD IN TIME.
SCROLL BACKWARD THROUGH DATA.
MOVE BACKWARD IN TIME.
567. 3
INPUT: TC-J
ALARM1: ON
Figure 10. Data Logging Screen Flow Chart
0.5ºC (0.9ºF)
1°C (1.8°F) or 0.5% of full scale
-100 to 760ºC (-148 to 1400ºF)
-100 to 1260ºC (-148 to 2300ºF)
-200 to 849°C (-328 to 1560°F)
-200 to 400ºC (-328 to 752ºF)
100 to 1760ºC (212 to 3200ºF)
0.06°C/°C
100 ohms Platinum, 2 or 3 wire, 0.00385
0.5ºC (0.9ºF)
-200 to 850ºC (-328 to 1562ºF)
Up scale
0.1% of Rdg
0 to 10 Vdc
0 to 20 mA and 4 to 20 mA
4 samples per second
90/240 Vac +/-10%, 50-400 Hz
0 to 50ºC (32 to 122ºF), 90% RH non-
NEMA-1/Type 1 Front bezel
48H x 96W x 118mm D (1.89 x 3.78 x 4.65")
45H x 92mm W (1.772 x 3.622")
295 g (0.65 lbs)
LINE GRAPH
DISPLAY
(REAL TIME)
567.3 °F
BASED ON
TIME/DATE OR
ALARM 1, 2
-OR-
LINE GRAPH
DISPLAY
REAL TIME
567.3 °F
LOGGING MODE
LINE GRAPH
DISPLAY
PAST TIME
LOGGING MODE
517.8 °F