Hitachi Relion RES670 Commissioning Manual page 40

Phasor measurement unit
Hide thumbs Also See for Relion RES670:
Table of Contents

Advertisement

Section 4
Starting up
Direct point-to-point link between PCM600 and the IED front port. The front port can be seen as a
service port.
A link via a station LAN or from remote via a network.
The physical connection and the IP address must be configured in both cases to enable communication.
The communication procedures are the same in both cases.
1.
If needed, set the IP address for the IEDs.
2.
Set up the PC or workstation for a direct link (point-to-point), or
3.
Connect the PC or workstation to the LAN/WAN network.
4.
Configure the IED IP addresses in the PCM600 project for each IED to match the IP addresses of
the physical IEDs.
Setting up IP addresses
Communication between the IED and PCM600 is enabled from the LHMI. The IP address and the
corresponding communication subnetwork mask must be set via the Ethernet configuration tool (ECT) for
each available Ethernet interface in the IED. Each Ethernet interface has a default factory IP address
when the IED is delivered. The IP adress and the subnetwork mask might have to be reset when an
additional Ethernet interface is installed or an interface is replaced.
DHCP is available for the front port, and a device connected to it can thereby obtain an automatically
assigned IP address via the local HMI path Main menu/ Configuration/ Communication/ Ethernet
configuration/ Front port/ DHCP.
Alternatively the default IP address for the IED front port is 10.1.150.3 and the corresponding subnetwork
mask is 255.255.255.0, which can be set via the local HMI path Main menu/ Configuration/
Communication/ TCP-IP configuration/ ETHFRNT:1Main menu/ Configuration/ Communication/
Ethernet configuration/ AP_FRONT.
Setting up the PC or workstation for point-to-point access to IEDs front port
An ethernet cable (max 2 m length) with RJ-45 connectors is needed to connect two physical Ethernet
interfaces together without a hub, router, bridge or switch in between.
1.
Select Search programs and files in the Start menu in Windows.
34
If an IED is equipped with optical LC interface, a converter between RJ-45 and LC is
needed.
© 2017 - 2022 Hitachi Energy. All rights reserved
1MRK 511 409-UUS Rev. K
Phasor measurement unit RES670
Commissioning manual