Cisco 3100 Series Hardware Installation Manual page 50

Secure firewall
Table of Contents

Advertisement

Network Equipment-Building System (NEBS) Statements
telecommunications equipment in the United States. It is not a legal or regulatory requirement, but rather an
industry requirement.
The following NEBS statements apply to the Secure Firewall 3120:
Note
Statement 7001 ESD Mitigation
This equipment may be ESD sensitive. Always use an ESD ankle or wrist strap before handling equipment.
Connect the equipment end of the ESD strap to an unfinished surface of the equipment chassis or to the ESD
jack on the equipment if provided.
Warning
Statement 7003—Shielded Cable Shielded Cable Requirements for Intrabuilding Lightning Surge
The intrabuilding port(s) of the equipment or subassembly must use shielded intrabuilding cabling/wiring that
is grounded at both ends.
The following port(s) are considered intrabuilding ports on this equipment:
Copper RJ-45 network ports
Warning
Statement 7005—Intrabuilding Lightning Surge and AC Power Fault
The intrabuilding port(s) of the equipment or subassembly must not be metallically connected to interfaces
that connect to the outside plant (OSP) or its wiring. These interfaces are designed for use as intrabuilding
interfaces only (Type 2 or Type 4 ports as described in GR-1089-CORE) and require isolation from the exposed
OSP cabling. The addition of primary protectors is not sufficient protection to connect these interfaces
metallically to OSP wiring.
This statement applies to the intrabuilding ports listed below:
Copper RJ-45 network ports
Warning
Statement 7012 Equipment Interfacing with AC Power Ports
Connect this equipment to AC mains that are provided with a surge protective device (SPD) at the service
equipment that complies with NFPA 70, the National Electrical Code (NEC).
Note
Statement 7013 Equipment Grounding Systems—Common Bonding Network (CBN)
This equipment is suitable for installations using the CBN.
Cisco Secure Firewall 3100 Series Hardware Installation Guide
46
Installation Preparation

Advertisement

Table of Contents
loading

This manual is also suitable for:

31053110312031303140

Table of Contents