Honeywell NOTIFIER PAN1-PLUS-EN3 Installation And User Manual page 3

Fire alarm devices - acoustic alarm device

Advertisement

Installation:
Connection
Connect the main output with "polarity inversion" to positive (A+) and negative (A-) terminals (see. Pict.1)
with a certified wire. Moreover, insert the end-of-line R resistor between the "A+" terminal and the "A-"
terminal. The value of the end-of-line R resistor depends on the kind of main installed, and it is indicated in
the main installation manual.
Terminal SYNC (Synchronism): if required, connect together the terminal SYNC of the devices to
synchronize them.
Terminals B+ B- (Buzzer Mute): if required, applying 24Vcc between B+ and B- or short-circuiting B- with A-,
the buzzer is silenced.
CONNECT THE MAIN
OUTPUT WITH POLARITY
INVERSION
Selection of backlight mode
DIP switch 1-2
OFF – OFF (Default)
ON - OFF
OFF - ON
ON - ON
Selection of sound pattern and power
DIP switch 3-4
OFF - OFF (Default)
ON - OFF
OFF - ON
ON- ON
Sound level
DIP switch 5-6
OFF- OFF (Default)
ON - OFF
OFF - ON
ON - ON
Wall fixing:
Fix the device on the wall through the 4 holes on its base (see Pict. 2).
Use an adapter to connect all cables in case of a system with external tubes.
The device must be placed with the long side parallel to the floor, and the acoustic speaker on the bottom.
Torx
Screws
NEGATIVE IN STANDBY
POSITIVE IN STANDBY
Pict. 1
Description
Backlight blinking at 0.6 Hz
Backlight OFF
Backlight OFF
Backlight ON
Description
983Hz pulsed at 1.2 Hz
Sweep from 1200 Hz to 500 Hz at 1.2Hz
983-750 Hz alternate at 1.2Hz
983Hz continuous
MAX Sound Level at 1 m
101 dB
97 dB
94 dB
Sound disabled (NOT COMPLIANT TO EN54-3)
Fixing Holes
R
SYNCRONISM
MUTE BUZZER
Pict. Pict.2